beautypg.com

Pump, Pump specifications, Installation specifications – Lochinvar ARMOR 151-200 User Manual

Page 4: Recommendation pump-rec-01 rev c

background image

4




PUMP RECOMMENDATION FOR

ARMOR 501-601 WATER HEATER

Pump Specifications

Part No.

HorsePower

Flanges

Valute Material

Flange Material

Vendor

Vendor Product Series

Orientation

PUM30003

2/5

2"

Bronze

Bronze

Armstrong

E Series

Vertical


Installation Specifications

Recommended for

Based on

Pump

Model Numbers

Minimum GPM

Installation Type

Armor Wtr Htr, AW(N,L) 501-601

53 GPM (501) & 53 GPM (601)

Single Water Heater piped to Single Storage Tank

PUM30003

Based on

Based on

Minimum Pipe Diameter

Connecting piping

2"

Maximum 45 feet straight pipe with 4-Elbows, 2-Unions and 2-Ball Valves

IMPORTANT: Read the Armor 151-801 Installation and Operation Manual. If the planned system exceeds
the pump capacity in flow and/or head see

“Pump-Curves-All Pumps” for alternate pumps and pump curves.

















PUMP

Recommendation