beautypg.com

Smart system control module – Lochinvar Power-fin 502 User Manual

Page 14

background image

User’s Information Manual

14

3

SMART SYSTEM control module

Status Display Screens

(cont’d)

By using the Previous/Next ( ,

) arrow keys on the SMART SYSTEM display panel, you can navigate through the nine (9)

display screens. Each screen will contain two (2) viewable items. The following is a description of the individual items and what
they can display:

Screen

Display shows:

Description

#3

SYS: ***F

If the system supply sensor has not been selected as the control sensor,
only the system temperature will be displayed.

***F (***)

When the system supply sensor has been selected as the control sensor,
the control will display the system temperature as well as the set point
in parenthesis.

Open

The control does not detect the system supply sensor.

Shorted

The system supply sensor wires or the sensor itself has become
shorted.

OUTDOOR: ***F

The control will display the outdoor air temperature as sensed by the
outdoor air sensor.

Open

The control does not detect the outdoor air sensor.

Shorted

The outdoor air sensor wires or the sensor itself has become grounded.

Press the Next

arrow key on the SMART SYSTEM display to access Screen #4.

#4

SYSRT: ***

The control will display the system return temperature if the system
return sensor is connected. If not connected, the display will skip this
screen and display screen #5.

VALVE: ***%

The control will display the position of the 3-way valve; 100% indicates
that no outlet water is being bypassed into the inlet.

Press the Next

arrow key on the SMART SYSTEM display to access Screen #5.

#5

FLUE: ***F

The control will display the flue temperature.

Open

The control does not detect the flue sensor.

Shorted

The flue sensor wires or the sensor itself has become shorted.

AUX: ***F

The control will display the temperature.

Open

The control does not detect the auxiliary sensor.

Shorted

The auxiliary sensor wires or the sensor itself has become shorted.

Press the Next

arrow key on the SMART SYSTEM display to access Screen #6.

#6

FAN SPD: ****RPM

The control will display the actual fan motor RPM.

FLAME SIG: **.*uA

The control will display the flame signal in dc microamps.

Press the Next

arrow key on the SMART SYSTEM display to access Screen #7.

This manual is related to the following products: