3 refrigerant planning values, Table 4 interconnecting piping refrigerant charge, Refrigerant planning values – Liebert Air Cooled User Manual
Page 16: Table 3, R-22 and r-407c refrigerant required, approximate, Table 4, Interconnecting piping refrigerant charge
Site Preparation
12
2.3
Refrigerant Planning Values
Planning for the refrigerant requirements of the completed system is the addition of the charges from
Indoor Unit, Condenser (including Lee-Temp receiver, if used) and the interconnecting piping.
Tables 3 and 4 provide the approximate charge required for the condensers and the interconnecting
piping. Consult indoor unit manuals for indoor unit charge requirements.
These values can be used for obtaining adequate refrigerant for the system, but should not be used for
final charging. Consult indoor unit manual for charging procedures.
Table 3
R-22 and R-407C refrigerant required, approximate
Standard
Condenser
Models
Approximate R-22 Refrigerant Needed
Approximate R-407C Refrigerant Needed
Single Circuit
lb (kg)
Dual Circuit
lb/circuit (kg/circuit)
Single Circuit
lb (kg)
Dual Circuit
lb/circuit (kg/circuit)
FSC or
VFD
Lee-Temp
(includes
receiver)
FSC or
VFD
Lee-Temp
(includes
receiver)
FSC or
VFD
Lee-Temp
(includes
receiver)
FSC or
VFD
Lee-Temp
(includes
receiver)
83
5 (2.3)
27 (12.3)
3 (1.4)
15 (6.8)
5 (2.3)
26 (11.8)
3 (1.4)
15 (6.8)
104
8 (3.6)
39 (17.7)
7 (3.2)
21 (9.5)
8 (3.6)
37 (16.8)
7 (3.2)
20 (9.0)
165
15 (6.8)
53 (24.0)
5 (2.3)
27 (12.3)
15 (6.8)
50 (22.7)
5 (2.3)
26 (11.8)
205
20 (9.1)
76 (34.5)
7 (3.2)
38 (17.2)
19 (8.6)
72 (32.7)
7 (3.2)
36 (16.3)
251
19 (8.6)
75 (34.0)
10 (4.6)
38 (17.2)
18 (8.2)
71 (32.23)
10 (4.6)
36 (16.3)
308
29 (13.2)
113 (51.3)
11 (5.0)
58 (26.3)
28 (12.7)
107 (48.5)
11 (5.0)
55 (24.9)
415
54 (24.5)
182 (82.6)
15 (6.8)
75 (34.0)
51 (23.1)
173 (78.4)
15 (6.8)
71 (32.2)
510
72 (32.7)
N/A
30 (13.6)
149 (67.6) 68 (30.8)
N/A
29 (13.2)
142 (64.4)
616
N/A
267 (121.3)
27 (12.3)
113 (51.3)
N/A
254 (115.2)
26 (11.8) 108
(49.0)
830
N/A
N/A
30 (13.6)
149 (67.6)
N/A
N/A
29 (13.2)
142 (64.4)
1010
N/A
N/A
60 (27.2)
154 (69.9)
N/A
N/A
57 (25.9)
147 (66.7)
Quiet-Line Condenser Models
63
N/A
39 (17.7)
N/A
21 (9.5)
N/A
37 (16.8)
N/A
20 (9.1)
119
N/A
50 (22.7)
N/A
27 (12.3)
N/A
48 (21.8)
N/A
26 (11.8)
127
N/A
76 (34.5)
N/A
38 (17.2)
N/A
72 (32.6)
N/A
36 (16.3)
143
N/A
126 (57.2)
N/A
64 (29.0)
N/A
120 (54.5)
N/A
61 (27.7)
214
N/A
161 (73.0)
N/A
81 (36.7)
N/A
153 (69.4)
N/A
77 (34.9)
286
N/A
196 (88.9)
N/A
125 (56.7)
N/A
186 (84.4)
N/A
119 (54.0)
409
N/A
N/A
N/A
129 (58.5)
N/A
N/A
N/A
125 (55.8)
572
N/A
N/A
N/A
196 (88.9)
N/A
N/A
N/A
186 (84.4)
Table 4
Interconnecting piping refrigerant charge
Line Size,
O.D., in.
R-22, lb/100 ft. (kg/30m)
R-407C, lb/100 ft. (kg/30m)
Liquid Line
Hot Gas Line
Liquid Line
Hot Gas Line
3/8
3.8 (1.7)
—
3.7 (1.7)
—
1/2
7.3 (3.3)
—
6.9 (3.1)
—
5/8
11.7 (5.3)
2.1 (1.0)
11.0 (5.0
2.2 (1.0)
3/4
16.6 (7.5)
3.0 (1.4)
15.7 (7.1)
3.1 (1.3)
7/8
24.4 (11.1)
4.4 (2.0) 23.0
(10.4) 4.5
(1.9)
1-1/8
41.4 (18.9)
7.8 (3.5) 39.3
(17.8) 7.8
(3.5)
1-3/8
63.3 (28.7)
11.8 (5.4) 59.8
(27.1 11.8
(5.4)
1-5/8
—
16.7 (7.6)
—
16.7 (7.6)