beautypg.com

Hydronic piping, Installation & operation manual – Lochinvar CREST 3.5 User Manual

Page 30

background image

30

Installation & Operation Manual

5

Hydronic piping

Please note that these illustrations are meant to show system piping concept only, the installer is responsible
for all equipment and detailing required by local codes.

NOTICE

Y-STRAINER

(RECOMMENDED)

(TYPICAL)

RELIEF

VALVE

(TYPICAL)

BALL VALVE

(TYPICAL)

AIR SEPERATOR

DRAIN PORT
(TYPICAL)

SYSTEM
CIRCULATOR

BACK FLOW
PREVENTER

PRESSURE
REDUCING VALVE

PRESSURE

GAUGE

EXPANSION

TANK

FROM SYSTEM

TO SYSTEM

MAKE UP
WATER

BOILER DRAIN

(TYPICAL)

Figure 5-5 Multiple Boilers - Alternate - Common Header - Full Flow

When installing multiple Crest boilers in full flow applications, utilize a reverse-return or other piping method
to ensure balanced flow through each boiler.