Maintenance schedule

5

ƽ WARNING Follow the maintenance procedures given throughout this manual. Failure to perform the service and

maintenance or follow the directions in this manual could result in damage to the boiler or system, resulting
in severe personal injury, death, or substantial property damage.

Service technician

(see the Crest Service Manual)

General:

• Address reported problems, if any

• Inspect interior; clean and vacuum if

necessary;

• Clean condensate trap and fill with fresh

water

Check for leaks (water, gas, flue,

condensate)

• Verify flue and air lines in good condition

and sealed tight

• Check system water pressure/system

piping/expansion

tank

• Check control settings

• Check ignition and flame sense

electrodes (sand off any deposits; clean

and

reposition)

• Check wiring and connections

Perform start-up checkout and

performance verification per Section 9.

• Flame inspection (stable, uniform)

• Check both flame signals (at least 10

microamps at high fire)

Clean the heat exchanger

Test low water cutoff (reference the

Crest Service Manual).

If combustion or performance
indicate need:

• Clean heat exchanger

Remove and clean burner using

compressed air only

• Clean the blower wheel

ANNUAL START-UP

Owner maintenance

(see pages 6 - 8 for detailed instructions)

Daily

• Check boiler area

Check pressure/temperature

gauge

Monthly

• Check vent piping

• Check air piping


• Check air and vent termination

screens

• Check relief valve

• Check condensate drain system


Every

6 months

• Test low water cutoff

• Reset button (low water cutoff)


• Check boiler piping (gas and
water) for leaks

• Operate relief valve

End

of season

months

• Shut boiler down (unless boiler

used for domestic hot water)

User’s Information Manual