Table 3-1 Troubleshooting Chart - No Display

FAULT

CAUSE

CORRECTIVE ACTION

No Display

- No 120 vac supplied to unit.

• Check external line switch, fuse, or breaker.

• Check position of ON/OFF switch. Turn switch to the

ON position.

• Check 120 vac through the ON/OFF switch.

• Check wiring harness connection between display

board and main control board. Connect
harness at both points.

- No voltage through the switch.

• Replace switch.

- Bad display board.

• Replace board.

- Bad main control board.

• Replace the main control board.

- Blown fuse.

• Replace fuse F3 on the main control board, see

page 33 of this manual.

No Burner

Operation

- Main control board temperature set point

satisfied.

• Review temperature setting.

- Remote thermostat satisfied.

• Review remote thermostat setting.

- Outside air temperature above Warm

Weather Shutdown (WWSD) set point for
main control board.

• Check location of outside air sensor. Check

resistance of outdoor air sensor and compare to Table
3-2B on page 35 of this manual.

- Unit locked out on fault.

• Consult display for specific fault. Refer to fault

descriptions on page 37 of this manual for corrective
actions.

Unit Does Not

Modulate

Above 50%

- Ramp delay active.

• Check ramp delay parameter settings. Optional PC

software required.

• Turn ramp delay feature off. See page 23 of this

manual for instructions on how to turn this feature off.

- Boiler controlled by BMS.

• Check BMS parameter settings. Optional PC

software required.

- Flue sensor open.

• Verify that the flue sensor is located in the flue outlet.

• Check wiring connections at the flue sensor.

• Check the resistance of the flue sensor and compare

to Table 3-2D on page 35 of this manual.