Non-concealed gas connections may be made using the

entry points on the base of the firebox. A concealed gas

connection may be made using the knockout hole in the

center back of the firebox. Select the most appropriate

entry point and knock out the relevant hole.

No more than 59" of 1/4" diameter pipe must be used

to avoid unnecessary pressure drops.

If a concealed gas connection is to be made, the supply

pipe should always be sleeved through walls and floors

using the shortest possible route.

For concealed supply pipe routing, pipes must (where

possible) be vertical and providing there is sufficient

wall thickness available, they should be placed in pipe

chases. Horizontal pipe runs should be avoided where

possible. Prior to chasing a solid wall, an inspection

should be made to note the proximity of any cables/

sockets outlets which may already be buried. Pipes

must be secured using suitable clips and protected

against corrosion. Ideally factory finished protected

pipe-work and fittings should be used. Joints should

be kept to a minimum and compression fittings must

not be used. The pipe-work installation must be tested

for soundness before any protection is applied and/or

the pipe-work and fittings are buried.

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE

Remove the wall mounting plate from the back of the appliance firebox by removing the

two retaining wing nuts (indicated by arrows in Figure 2) from the retaining studs that

protrude into the lower part of the main firebox.

11.0 PREPARING THE APPLIANCE

Figure 2

Wall Mounting Plate

Firebox

10.0 GAS SUPPLY ROUTES

IMPORTANT NOTE: All gas piping must be done by

a licensed plumber or gas fitter and must conform

to the requirements of the National Fuel Gas Code

NFPA 54 / ANSI Z223.1 - latest edition.

Gas connection: The heater gas inlet connection is

3/8” NPT at the regulator, located below the burner,

in the right hand side of the heater. There are four

possible entry points for the gas supply pipe-work

to enter the appliance firebox. These entry points

are ‘knock out’ type holes (shown in Figure 1).

Figure 1 - Gas Supply Entry Points