Optional network connection, Network with hub, Network daisy-chain – Linear AE-1000 User Manual

Page 15

background image

15

220777 C IMAGE 15

Optional Network Connection

Linear’s AE-1000, AE-2000, & AM-3 Access Control Systems can
be connected together in a network. A network will allow sharing
programming and user information between the systems.
Network wiring conforms to 3-wire RS-485 electrical specifi cations. Units
connected in the network can be wired using one unit as a “hub” or by
wiring from one unit to the next in “daisy-chain” fashion. See the fi gures
for wiring options.

• Use Belden 9925 or Carol C0600 shielded cable or equivalent.

Maximum wire run distance is 4000 feet.

NOTE: Be sure to connect the cable’s shield to one of the GND

terminals.

Network with Hub

1. Mount and install the units for the network.
2. Choose one unit to be the Network Hub. Usually this would be a

centrally located or “main” unit.

3. Route 3-conductor shielded cable from the hub unit to one of the

other units. Repeat this step to connect the hub unit to each of the
other units.

4. Connect the 3-conductor cable to each unit’s NETWORK

terminals.

Network Daisy-chain

1. Mount and install the units for the network.
2. Route 3-conductor shielded cable from one unit to the next unit

until there is cabling run to all of the units.

3. Connect the 3-conductor cable to each unit’s NETWORK

terminals.

NET-A

GND

NET-B

NETWORK

UNIT "3"

NET-A

GND

NET-B

NETWORK

UNIT "4"

NET-A

GND

NET-B

NETWORK

MASTER

UNIT "1"

NET-A

GND

NET-B

NETWORK

UNIT "2"

ACCESS CONTROL HOMERUN NETWORK

USING ONE UNIT AS A NETWORK MASTER

NOTE: GROUND
CABLE SHIELDS
ONLY AT ONE END

SHIELD

SHIELD

SHIELD

NET-A

GND

NET-B

NETWORK

UNIT "3"

NET-A

GND

NET-B

NETWORK

UNIT "4"

NET-A

GND

NET-B

NETWORK

MASTER

UNIT "1"

NET-A

GND

NET-B

NETWORK

UNIT "2"

ACCESS CONTROL

NETWORK USING

"DAISY CHAIN"

WIRING

S

HI

EL

D

S

HI

EL

D

SHIELD

NOTE: GROUND
CABLE SHIELDS
ONLY AT ONE END