beautypg.com

Installation, Electrical output connections, Welding cable connections – Lincoln Electric POWER-ARC 4000 User Manual

Page 12

background image

A-5

INSTALLATION

POWER-ARC 4000

A-5

ELECTRICAL OUTPUT
CONNECTIONS

See Figure A.1 for the location of the current control
dial, weld output terminals, ground stud, circuit
breakers, 240 and 120 volt receptacles.

WELDING CABLE CONNECTIONS

Cable Size and Length

Be sure to use welding cables that are large enough.
The correct size and length becomes especially
important when you are welding at a distance from
the welder.

Table A.1 lists recommended cable sizes and lengths
for rated current and duty cycle. Length refers to the
distance from the welder to the work and back to the
welder. Cable diameters are increased for long cable
lengths to reduce voltage drops.

TABLE A.1

RECOMMENDED WELDING CABLE

SIZE AND LENGTH

TOTAL COMBINED LENGTH OF ELECTRODE AND

WORK CABLES

Cable Size for

125 amp/

Cable Length

30% Duty Cycle

0-50 feet (0-15 meters)

6 AWG

50-100 feet (15-39 meters)

4 AWG

100-150 feet (30-46 meters)

3 AWG

150-200 feet (46061 meters)

2 AWG

200-250 feet (61-76 meters)

1 AWG

POWER ARC 4000

ELECTRODE SELECTION GUIDE

80

90

100

70

AMPS

AMPS

AMPS

AMPS

WARNING

AMPS

125

GENERATOR

6

5

4

3

2

1

FIGURE A.1 - POWER-ARC 4000 OUTPUT CONNECTIONS

1. CURRENT CONTROL DIAL
2. WELD OUTPUT TERMINALS (2)
3. GROUND STUD

4. CIRCUIT BREAKERS (2) - 20 AMP
5. RECEPTACLE - 240 VOLT, 20 AMP
6. DUPLEX RECEPTACLE - 120 VOLT, 20
AMP