beautypg.com

Lennox International Inc. MONTECITO ESTATE MONTEST User Manual

Page 13

background image

8. A rain cap must be installed on top of the chimney. Failure to install

a rain cap may cause corrosion problems.

9. Cut and frame square holes in all floors, ceilings, and roof that the

chimney will go through to provide a 2” (50 mm) clearance between

the chimney and any combustible materials. Do not fill this 2” space

with insulation or any other combustible material.

10. Portions of the chimney which may extend through accessible spaces

must be enclosed to avoid contact with combustible materials or

damage to the chimney.

11.When offsets are used, the pipe may not penetrate a ceiling or floor

unless it is running vertical (no 30° offsets).

Figure 21

THE CHIMNEY SYSTEM

Chimney Installation Notes

1. If possible, install an interior chimney as it will provide better per-

formance. In areas with continuous temperatures below 18°C (0°F),

the use of an exterior chimney increases the likelihood of operating

problems such as low draft, high rate of creosoting, and poor start-up

characteristics. Exterior chimneys are also prone to down-drafting

and flow reversal. Installations which are located on lower floors in

the house, such as in a basement, in combination with an outside

chimney, are especially prone to flow reversal.

2. The fireplace model MONTEST may be installed only with Security

Chimneys International Ltd 7” dia. chimney systems model Secure

Temp™

S2100+ / Nova Temp™

HT6000 / Secure Temp GX (U.S. only)

or ACBI.

3. A chimney venting a fireplace shall not vent any other appliance.

4. The minimum chimney height is 12 feet (3.7 m) excluding the fire-

place.

5. All chimney installations must include at least one support in order to

be able to take any lateral load. The maximum chimney length that

can be supported by the fireplace is nine (9) feet (2.75 m) for Secure

Temp

S2100+ / Nova Temp

HT6000+ / Secure Temp

GX and 26 feet

(8m) for ACBI chimney. In altitude, add 18” (450 mm) to the chimney

for every 2,000 feet (600 m) above sea level.

6. The chimney must extend at least three (3) feet (915 mm) above its

point of contact with the roof and at least two (2) feet (610 mm) higher

than any wall, roof or building within ten (10) feet (3 m) of it (Figure

21).

7. If the chimney extends higher than five (5) feet (1,500 mm) above

its point of contact with the roof, it must be secured using a roof

brace.

ten (10) feet

three (3) feet Min.

two (2) feet Min.

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

13