No cooling and heating operation performed – LG LF300CP(LP-C303R20) User Manual
Page 28
–28–
PACKAGE AIR CONDITIONER VOLTAGE LIMITS
No cooling and heating operation performed
NAME PLATE RATING
MINIMUM
MAXIMUM
380 V
342 V
418 V
220 V
198 V
242 V
380 - 415 V
342 V
456 V
2) Only blowers do not work
WHAT TROUBLED
COMPLAINTS
HOW TO CHECK
REMEDY
Other parts than the unit
Magnetic switch for
compressor & fan motor
Operating switch
Protection devices
Electric supply interrupted
Defective power wiring Cut
of power fuse
Too low voltage
Control point is on
condition of "OFF" due to
trouble.
Troubled or defective
contactor
Opened the contact point
with trouble
Measure it with a tester in
case that the same
power source is supplied
to other equipment than
the unit, what and where
trouble can be discovered
by checking the operation
of other equipment.
Measure it with a tester.
Make short-circuit, then
measure it with a tester.
Check it with the eyes or
tester.
Check it with the eyes or
tester.
Repair a switch box and
is relative instrument.
Replacement of fuse
Request a power
supplier to repair.
Check the power source.
Use a thick cable if
necessary.
Replace it if necessary.
Repair or replace it.
Discover the trouble
cause and push the rest
button.
WHAT TROUBLED
COMPLAINTS
HOW TO CHECK
REMEDY
Air volume change over
switch
Capacitor
Troubled or defective
contact point
Defected
Check it with the eyes or a
tester
Check it with a tester.
Repair or replace it.
Replace it.