Troubleshooting, Before troubleshooting, Check the following – Lochinvar KNIGHT 801 User Manual

Page 33: Check control module fuses

background image

3

Troubleshooting

33

Label all wires prior to disconnection
when servicing controls. Wiring errors
can cause improper and dangerous
operation. Always disconnect power
to the boiler before servicing. Failure
to comply could result in severe
personal injury, death, or substantial
property damage.

Never jumper (bypass) any device
except for momentary testing as
outlined in the Troubleshooting
chart. Severe personal injury, death,
or substantial property damage can
result.

Before troubleshooting:

1. Have the following items:

a.

Voltmeter that can check 120 VAC, 24 VAC, and

12

VDC.

b. Continuity

checker.

c. Contact

thermometer.

2. Check for 120 VAC (minimum 102 VAC to maximum

132 VAC) to boiler.

3. Make sure thermostat is calling for heat and contacts

(including appropriate zone controls) are closed.

Check for 24 VAC between thermostat wire nuts and
ground.

4. Make sure all external limit controls are installed and

operating.

Check the following:

1. Wire connectors to control module are securely

plugged in at the module and originating control.

2. Gas

pressures:

• Maximum: 14 inches w.c. (3.5 kPa) (natural and
LP) with no flow (lockup) or with boiler on
• Minimum: 4 inches w.c. (1.0 kPa) (natural),
8 inches w.c. (2.0 kPa) (LP) with gas flowing (verify
during boiler startup)

Check control module fuses

ALWAYS check control module fuses before
replacing control module or any major
components (blower, etc.). If one of these
fuses is blown, it can prevent the control
module or other components from operating.

1. Turn OFF the power to the boiler at the external line
switch.

2. Remove top access cover.

3. Remove the control module cover.

4. Inspect fuses F1, F2, and F3, see FIG 3-1 below.

F3 - .80 AMP FUSE

24V DC POWER SUPPLY

F1 - 5 AMP FUSE

PUMPS

F2 - 3.15 AMP FUSE

BLOWER

Figure 3-1 Control Module Fuses

5. The boiler is shipped with three (3) spare fuses in a plastic

bag attached to the control module cover.

6. If necessary, replace open fuse (F3 is .80 amps, F2 is 3.15

amps and F1 is 5 amps).

Note: Fuses F1, F2, and F3 are all slow blow fuses.

Do not jumper fuse or replace with any fuse
except as specified. Failure to comply could
result in severe personal injury, death, or
substantial property damage.

7. Install control module cover and top access cover after fuse

inspection.

8. Restore power to the boiler at the external line switch and

verify boiler operation (Section 10 - Start-up in the Knight
XL Installation and Operation Manual) after completing
boiler service.