NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
C
himney
r
equirements
The Performer™ C/A210 inserts are approved for use in
masonry fireplaces built to UBC Chapter 37 or equivalent
with a minimum 22” (559mm) opening at the front of the
fireplace.
These heaters are designed to be installed into an existing
masonry fireplace (built to UBC 37 or ULC S628 standards)
or factory-built, solid-fuel and wood-burning fireplaces (listed
to UL 127 or ULC S610) only.
Do not remove brick or mortar from masonry fireplace to
accommodate insert. Do not remove brick or mortar from
masonry fireplace to accommodate insert. Approved with or
without positive flue connection. Approved with minimum
6” (152mm) diameter stainless steel listed reline system.
Ask your dealer for recommended chimney size. Country
Collection inserts are tested to UL 1482 / ULC S628-93 and
listed by OMNI-Test Laboratories, Inc.; Beaverton, OR.
Remove and clean behind unit frequently, as creosote build
up may occur rapidly.
i
nstallation
P
roCeDures
- m
asonry
C
himney
Note: Although not required, a full-length stainless steel liner
is recommended for optimum safety and performance. See
your Lennox Hearth Products dealer for details.
Note: When installing your stove with a positive flue connec-
tion, be sure to leave the insulation off the surround panels
(flanges) and leave a 1/4” (6mm) airspace insulation off the
surround panels and the facing of your fireplace.
1. READ ENTIRE INSTALLATION INSTRUCTIONS.
2. Check all REQUIRED CLEARANCES as specified in the
previous section (page 7) of this installation instruction
booklet.
3. Wear gloves during installation in case of sharp edges on
the stove and it’s parts
4. Determine the depth of the fireplace lintel. The lintel is
the masonry area over the fireplace opening, and is sup-
ported by a noncombustible plate, usually of steel. The
depth may vary from a single brick width (4”/102mm)
to that of several brick. If any portion of the flue collar
opening on top of the insert (as shown in the diagram
below) will project under the lintel area, a deflector plate
must be mechanically attached to the fireplace insert to
divert heat and gases away from the lintel.
Consult your dealer for the correct attachment piece.
Compare lintel depth to the distance from the flue collar
opening to the fireplace to determine if this caution per-
tains to your installation. If there is sufficient clearance,
a flue offset may also be used. Consult your dealer.
5. Open or remove the existing fireplace damper. Make sure
the damper cannot fall closed.
6. Install the two 1/2” x 3” (13mm x 76mm) leveling bolts
-heads up- a few turns in the leveling nuts on each side
of the outer chamber of the insert at the lower rear cor-
ners.
7. Position the insert in the center of the fireplace opening
and push it back until the surround brackets are approxi-
mately 2” (51mm) away from the fireplace front.
8. Install the side surround panels and push the insert up
snug against the fireplace face. Then with the location
selected remove the surround panels and level the stove
with the leveling bolts using a 3/4” (19mm) socket, exten-
sions (to reach the bolt head), and a ratchet.
9. Glue the insulation around the outer edge of both the top
and side surround panels.
10. Install the surround panels loosely, align and tighten.
Check for a tight fit against the fireplace.
11.Install the brick and baffle as per instructions on page
6.
POSITIVE FLUE CONNECTION: See your authorized Len-
nox Hearth Products dealer for necessary accessories and
installation instructions.
Positive flue connectors required for installation in Canada
are available from your Lennox Hearth Products dealer.
Please use the part number indicated below.
71161 - 6" Positive Flue Connector Ring Kit
Lintel
Flue Outlet
Not to Scale
Brick Face
Insert Surround
Smoke
Deflector
Mechanically
Attached to
Insert
Figure 7