Troubleshooting – Lochinvar Knight Heating Boiler 81-286 User Manual

Page 45

background image

3

Troubleshooting

(continued)

Service Manual

45

Table 3-4 (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface

FAULT

DESCRIPTION

CORRECTIVE ACTION

Outlet Temp

High

(continued)

Outlet water temperature has exceeded the
maximum outlet water temperature.

• Verify that the boiler pump is set to the proper speed
or that the boiler pump is the proper size. Reference
Section 6 - Hydronic Piping of the Knight Boiler
Installation and Operation Manual for boiler pump
specifications.

• Replace the main control board.

Rem Ctrl Flt

External control is cycling too often.

• Check set point of the external control.

• Check the wiring between the external control and the
unit.

• Replace the control.

Parameters

Progr

(will require a manual

reset once the condition

has been corrected. Press

the RESET button on the
SMART SYSTEM

display

to reset.)

After downloading parameters from a laptop,
the main control board must be reset.

• Press the ENTER/RESET button on the SMART
SYSTEM display panel.

Service Blk

While the unit is in Service Mode, the outlet
temperature has exceeded 185°F.

• Establish a heating load to remove the heat from the
boiler

loop.

• Verify that the system is full of water and that all air
has been properly purged from the system.

• Verify that the boiler is piped properly into the heating
system. Refer to Section 6 - Hydronic Piping of the

Knight Boiler Installation and Operation

Manual for the proper piping methods for the Knight
boiler.

• Check 120 vac to the boiler pump motor on a call for
heat. If voltage is not present, check the wiring back
to the main control board. Replace the main control
board if necessary.

• If 120 vac is present on a call for heat and the boiler
pump is not operating, replace the pump.

• Verify that the boiler pump is set to the proper speed
or that the boiler pump is the proper size. Reference
Section 6 - Hydronic Piping of the Knight
Boiler Installation and Operation Manual for boiler
pump

specifications.