32

Installation & Operation Manual

5

Hydronic piping

HOT WATER
GENERATOR

SYSTEM
CIRCULATOR

AIR
SEPERATOR

MAKE UP
WATER

DRAIN POINT
(TYPICAL)

SYSTEM SUPPLY
SENSOR

BALL VALVE
(TYPICAL)

HEAT EXCHANGER 2
BOILER PUMP

PRESSURE RELIEF
VALVE

FLOW CHECK
VALVE (TYPICAL)

PRESSURE REDUCING
(VALVE)

EXPANSION
TANK

UNION (TYPICAL)

TEMPERATURE/
PRESSURE GAUGE

WATER GENERATOR
CIRCULATOR
(TYPICAL)

BACK FLOW
PREVENTER

PRESSURE GAUGE

HEAT EXCHANGER 1
BOILER PUMP

Y-STRAINER

(RECOMMEND)

(TYPICAL)

MAY SUBSTITUTE LOW LOSS HEADER

TO

SY

STE

M

TO FLOOR
DRAIN

FR

OM

SY

STE

M

Figure 5-5 Single Boiler - Primary/Secondary Piping

NOTICE

System flow should always remain higher than the required flow for the boiler(s) when the boiler(s) is in
operation to prevent short cycling and high limit issues.

NOTICE

A system supply sensor (factory
supplied) MUST BE installed for proper
boiler operation.

Please note that these illustrations are meant to show system piping concept only, the installer is responsible
for all equipment and detailing required by local codes.

NOTICE