prescribed temperature-pressure relief valve installed in the

designated opening in the water heater in place of the factory

furnished valve.

For safe operation of the water heater, the relief valve must not

be removed from its designated opening nor plugged.

The temperature-pressure relief valve must be installed directly

into the fitting of the water heater designed for the relief valve.

Position the valve downward and provide tubing so that any

discharge will exit only within 6 inches (153 mm) above, or at any

distance below the structural floor. Be certain that no contact is

made with any live electrical part. The discharge opening must

not be blocked or reduced in size under any circumstances.

Excessive length, over 30 feet (9.14 m), or use of more than

four elbows can cause restriction and reduce the discharge

capacity of the valve.

No valve or other obstruction is to be placed between the

relief valve and the tank. Do not connect tubing directly to

discharge drain unless a 6 inch air gap is provided. To prevent

bodily injury, hazard to life, or property damage, the relief

valve must be allowed to discharge water in quantities should

circumstances demand. If the discharge pipe is not connected

to a drain or other suitable means, the water flow may cause

property damage.

The Discharge Pipe:

• Shall not be smaller in size than the outlet pipe size of the

valve, or have any reducing couplings or other restrictions.

• Shall not be plugged or blocked.

• Shall be of material listed for hot water distribution.

• Shall be installed so as to allow complete drainage of both the

temperature-pressure relief valve, and the discharge pipe.

• Shall terminate at an adequate drain.

• Shall not have any shut-off valve between the relief valve and

tank nor in the discharge pipe.

The temperature-pressure relief valve must be manually

operated at least once a year. Caution should be taken to

ensure that (1) no one is in front of or around the outlet of the

temperature-pressure relief valve discharge line, and (2) the

water manually discharged will not cause any bodily injury or

property damage because the water may be extremely hot.

If after manually operating the valve, it fails to completely

reset and continues to release water, immediately close

the cold water inlet to the water heater, follow the draining

instructions, and replace the temperature-pressure relief

valve with a new one.

FIGURE 10.

Filling the Water Heater

Never use this water heater unless it is completely full of water.

To prevent damage to the tank and heating element, the tank

must be filled with water. Water must flow from the hot water

faucet before turning “ON” power.

To fill the water heater with water:

• Close the water heater drain valve by turning the handle to

the right (clockwise). The drain valve is located on the lower

front of the water heater.

• Open the cold water supply valve to the water heater.

NOTE: The cold water supply valve must be left open

when the water heater is in use.

• To insure complete filling of the tank, allow air to exit by

opening the nearest hot water faucet. Allow water to run until

a constant flow is obtained. This will let air out of the water

heater and the piping.

• Check all new water piping for leaks. Repair as needed.