beautypg.com

Troubleshooting guide, Start up conditions – Kenmore 153.338073 User Manual

Page 23

background image

23

TROUBLESHOOTING GUIDE

Start Up Conditions

Thermal Expansion

Water supply system may, because of such events as high line
pressure, frequent cut-offs, and the effects of water hammer
have installed devices such as pressure reducing valves, check
valves, back flow preventers, etc., to control these types of
problems. When these devices are not equipped with an internal
by-pass, and no other measures are taken, the devices cause
the water system to be closed. As water is heated, it expands
(thermal expansion) and closed systems do not allow for the
expansion of heated water.

The water within the water heater tank expands as it is heated
and increases the pressure of the water system. If the relieving
point of water heater’s temperature-pressure relief valve is
reached, the valve will relieve the excess pressure. The
temperature-pressure relief valve is not intended for the
constant relief of thermal expansion.
This is an unacceptable
condition and must be corrected.

It is recommended that any devices installed which could create
a closed system have a by-pass and/or the system have an
expansion tank or device to relieve the pressure built by thermal
expansion. Thermal expansion tanks are available from Sears
stores and through the Sears Service Centers. Contact the local
plumbing inspector, water supplier and/or the Sears Service
Center for assistance in controlling these situations, see Figure
26 and Figure 26 A.

FIGURE 26.

FIGURE 26A.

Thermal Expansion Tank Specifications

Tank Dimensions

Pipe

Model

Capacity in Inches

Fitting

Number

In Gallons

Diameter

Length

On Tank

153.331050

5

11 (279 mm)

14-3/4 (375 mm)

3/4” Male

NOTE: Expansion tanks are pre-charged with a 40 psi air
charge. If the inlet water pressure is higher than 40 psi, the
expansion tank’s air pressure must be adjusted to match
that pressure, but must not be higher than 80 psi.

Strange Sounds

Possible noises due to expansion and contraction of some metal
parts during periods of heat-up and cool-down do not represent
harmful or dangerous conditions.

Condensation causes sizzling and popping within the burner
area during heating and cooling periods and should be
considered normal. See Condensation section.

Draft Hood Operation

Check draft hood operation by performing a worst case
depressurization of the building. With all doors and windows
closed, and with all air handling equipment and exhaust fans
operating such as furnaces, clothes dryers, range hoods and
bathroom fans, a match flame should still be drawn into the
draft hood of the water heater with its burner firing. If the flame
is not drawn toward the draft hood, shut off water heater and
make necessary air supply changes to correct.

Condensation

Whenever the water heater is filled with cold water, some
condensate will form while the burner is on. A water heater may
appear to be leaking when in fact the water is condensation.
This usually happens when:

This manual is related to the following products: