beautypg.com

Installation instructions, Installation locations – Kidde KN-COPF-I User Manual

Page 7

background image

• With 18 alarms interconnected, it is still possible to interconnect up to

a total of six remote signaling devices and/or relay modules.

• The maximum wire run distance between the first and last unit in an

interconnected system is 1000’ (305 m).

• Make certain alarms are wired to a continuous, (non-switched) power

line. NOTE: Use standard UL-listed household wire (as required by local
codes) available at all electrical supply stores and most hardware
stores.

Wiring

The diagram above illustrates interconnection wiring. Improper connec-
tion will result in damage to the alarm, failure to operate, or a shock
hazard.

CAUTION: Turn off the main power to the circuit before wiring
the alarm.

Wires on the AC Quick-Connector Alarm Harness:

Black

Connected to live (L) side of AC line

White

Connected to neutral (N) side of AC line

Red

Connected to interconnect lines (red wires) of other units
in a multiple-station set-up

4. Installation Instructions

Interconnecting

CAUTION: Kidde (Fyrnetics/Lifesaver/Kidde/Nighthawk/Pyrene)
alarms and accessories can only be interconnected with other
Kidde alarms and accessories. Connection of these devices to
another manufactures interconnect system, or connection with
equipment from another manufacturer into an existing Kidde
interconnect system could result in nuisance alarming, failure to
alarm, or damage to one or all of the devices in the interconnect
system.

• When compatible Kidde smoke alarms and heat alarms are

interconnected to your CO alarm, they will only respond to a smoke
or heat related event.

• When mixing Kidde alarms which have battery back-up with models

without battery back-up, be advised that the models without battery
back-up will not function during an AC power failure.

• For alarms that are being used as single station alarms, do not

connect the red wire to anything. Leave the red wire insulating cap in
place to make certain that the red wire cannot contact any metal
parts or the electrical box.

• The appropriate power source is 120 Volt AC Single-Phase supplied

from a non-switchable circuit, which is not protected by a ground
fault interrupter.

• All interconnectable alarms should be installed on a UL-listed or

recognized junction box. All connections should be made by a
qualified electrician and must conform to article 760 of the U.S.
National Electrical Code, NFPA 72 and/or any other codes having
jurisdiction in your area.

• When alarms are interconnected, all interconnected units must be

powered from a single circuit.

• A maximum of 24 Kidde devices may be interconnected in a multiple-

station arrangement. The interconnect system should not exceed the
NFPA interconnect limit of 12 smoke alarms and/or 18 alarms total
(smoke, CO, smoke/CO combination, heat, etc.).

4. Installation Instructions

FUSE OR CIRCUIT BREAKER

RED

BLACK

WHITE

CONNECTOR

First CO Alarm

Additional

CO Alarm

Optional

Accessory

(See list of compatible

Kidde devices)

Interconnect Wiring Diagram

• Do not obstruct the vents located on the alarm. Do not place the

alarm where drapes, furniture or other objects block the flow of air to
the vents.

3. Installation Locations