beautypg.com

Inspection and maintenance schedule, General recommendations – SPX Cooling Technologies MARLEY CLASS F400 User Manual

Page 18

background image

18

inspection and maintenance schedule

General Recommendations

—more frequent inspection and maintenance may be desirable

D–Daily W–Weekly M–Monthly Q–Quarterly S–Semiannually Y–Yearly R–as Required

1. Inspect for clogging

M M

W

W

2. Check for unusual noise or vibration

D

D D

D

3. Inspect keys, keyways and set screws

S

S

S

S

4. Make sure vents are open

S

5. Lubricate (grease)

R

S

6. Check oil seals

M

7. Check operating oil level

D

8. Check static oil level

M

9. Check oil for water and sludge

M

10. Change oil

S

11. Check fan blade tip clearance

S

12. Check water level

D

D

13. Check for leakage

W

S

S

S

14. Inspect general condition

S

S

S

S

Y

S

Y

S

Y

S

S

S

Y

S

S

S

15. Tighten loose bolts

S

S

S

S

16. Clean

R

R

R

R

R

R

S

R

R

R

R

17. Repaint

R

R

R

R

18. Rebalance

R

R

19. Inspect/repair for safe use

Y

Y

Y

20. Inspect and repair before each use

R

Fan and Fan Guard

Motor

Driveshaft and Guards

Geareducer

Eliminator

Fill

Cold W

ater B

asin

Hot W

ater Distribution System

Float V

alve

Suction Screen

Control V

alves

Structural Members

Casing

Fan Cylinder

St

airs, Ladders, W

alkway

, Doors, Handrails

Davits, Derric

ks, Hoists