Key functions, 13 of 20, Engineer reset – Security Systems TS2000 User Manual
Page 13: Loading defaults, Bell test/walk test, Control panel links fuses

TS2000
Key Functions
Engineer Reset
1.
Enter your engineer’s code default 1234, you are
now in Engineer’s Mode
2.
Press 0 in quit to unset.
Loading Defaults
1.
Power down panel battery and mains, close LK2
2.
Power up panel battery and mains
3.
Enter 1234 and open LK2
4.
The panel is back to Factory Default Programming.
Bell Test/Walk Test
Please refer to page 19
Memory Default Values
When a CP is shipped from the factory the memory data
default parameters are set to:
1.
Circuits: The Type and Attributes Parameters set will
depend upon the number of circuits detected;
2.
Passcodes: Engineer 1234: Master 5678: Others
unspecified;
3.
Timers: Exit 25 secs: Exit Settling 5 secs: First Entry 30
secs: Second entry 30 seconds: Bell delay 5 mins:
Bell Duration 20 mins: Comms Delay 1.5 mins: Lights
Off 5 secs: Mains Off 10 secs: Menu Timeout 30 secs:
Double Knock 10 secs.
These values will also be restored if a Factory Restart
occurs.
Control Panel Links
Fuses
496529 Issue A
13 of 20
TS2000
Link
Functions
LK1
Open: Printer to monitor Network
activity
Closed: Normal; Printer normal
and responds to keypad
commands
LK2
Open: Normal; On-site restart at
power up
Closed:Factory restart at power
up
LK3
DC3 Monitor; Leave closed
JP5
Normally fitted with links
Remove and fit Engineer’s REM if
required.
JP9
Open: Novram battery isolated
Closed: Normal; Novram battery
connected
JP13
Open: Normal
Closed: Soft reset
Fuse
Value
Use
PSU F1
1AQB
Low voltage
ac input
PSU F2
2A QB
12V external
(auxiliary)
supply
Fuseholder
1A QB
Network 12V
supply
Fused terminal
Block
1A
Mains input