Multirecord area, Table 32: fru device product information area – SSI America EPS2U User Manual
Page 29
SSI
EPS2U Power Supply Design Guide, V2.1
8.3.2.2 MultiRecord
Area
Implement as defined by the IPMI FRU document. The following record types shall be used on this power supply:
• Power Supply Information (Record Type 0x00)
• DC Output (Record Type 0x01)
• No other record types are required for the power supply.
MultiRecord information shall be defined as follows:
Table 32: FRU Device Product Information Area
Field Name (PS Info)
Field Information Definition
Overall Capacity (watts)
480
Peak VA
550
Inrush current (A)
50
Inrush interval (ms)
5
Low end input voltage range 1
90
High end input voltage range 1 140
Low end input voltage range 2
180
High end input voltage range 2 264
A/C dropout tol. (ms)
20
Binary flags
Set for: Hot Swap support, Autoswitch, and PFC
Peak Wattage
Set for: 10 s, 550 W
Combined wattage
Set for 5 V & 3.3V combined wattage of 115 W
Predictive fail tach support
Not supported, 00h value
Field Name (Output)
Field Description:
Five outputs are to be defined from #1 to #5, as follows: +3.3 V, +5
V, +12 V, -12V, and +5 VSB.
Output Information
Set for: Standby on +5 VSB, No Standby on all others.
All other output fields
Format per IPMI specification, using parameters in the EPS12V
specification.
- 29 -