Temporary timer to extend the comfort mode, Button lock, Reminder to clean filters and for external faults – Siemens rdf600kn User Manual
Page 2: Note: economy mode, Control sequence, Recalibrating the sensor, Control parameters
CE1B3171.1en / 2012-08-29
Subject to change
Siemens Building Technologies
Temporary timer to extend the Comfort mode
When Economy mode is active, press operating mode button to tempo-
rarily return to Comfort mode. symbol appears. Press operating mode
button again to stop the timer.
You can only extend Comfort mode if parameter P02 = 1.
Duration * : P68 = 0...360 min, factory setting = 0 min.
Button lock
Press operating mode button for 3 seconds to lock or unlock the buttons if
manual button lock is configured (parameter P14 = 2).
The thermostat automatically locks the buttons 20 seconds after the last
adjustment if "Auto lock" is configured (P14 = 1).
The key symbol
indicates locked buttons.
Reminder to clean filters and for external faults
FIL *
AL1 *
AL2 *
This message reminds you to clean your HVAC equipment filters.
It is displayed after ………… “fan operating hours” and disappears when the
thermostat is set to Protection ( ).
These messages inform you on external faults *:
AL1 : ...……………………… AL2 : ...………………………………….
Note: Economy mode
The Economy setpoints are factory-set to 15 °C for heating and 30 °C for
cooling. Use parameters P11 and P12 to adjust the values.
Important: You can set these setpoints to OFF; the thermostat then is
inactive, i.e. no protective heating or cooling function.
Risk of frost!
Commissioning
You can adjust a number of different control parameters to adapt the thermostat to your
system and optimize control performance. You can do this during operation either via the
buttons on the thermostat or using a commissioning tool.
Control sequence
Recalibrating the sensor
* Needs to be configured by your HVAC installer
Control parameters
Proceed as follows to change the most important control parameters:
(Your HVAC installer can set additional parameters)
+ / –
1. Press the – and + buttons simultaneously at least 4 seconds.
Release, and within 2 seconds, press + again until "P01" is displayed.
2. Repeatedly press the + or – button to select the required parameter.
P01
P02
P08
P14
+
-
+
-
-
+
3171z99
End
-
+
-
P13
+
-
3. Press + and – simultaneously. The current value of the selected parameter begins to flash, allowing you to change
the value by repeatedly pressing + or –.
4. The next parameter is displayed when you press + and – again simultaneously.
5. Repeat steps 2 to 4 to display and change additional parameters,.
6. Press + or – until “End” is displayed, and then press + and – simultaneously to save the change and exit parameter
entry mode.
15 minutes after the last display or setting, all changes are saved and the thermostat leaves parameter setting mode.
Para-
meter
Description
Factory setting
Setting range
Adj
P01 Control
sequence
2-pipe: [0…3]
1 (Cooling only)
4-pipe: [2…4]
4 (Heating&Cooling)
0 = Heating only
1 = Cooling only
2 = Manual H or C
3 = Auto Changeover
4 = Heating & cooling
P02
Mode selection by user via operating mode button
1 (Auto **,
Protection)
1 = Auto **, Protection
2 = Auto **, Comfort, Economy,
Protection
P04
Selection of °C or °F
0 (°C)
0 = °C
1 = °F
P05 Sensor
calibration
0.0 °C
– 3 ... +3 °C
P06
Standard temperature display
0 (Room temp.)
0 = Room temperature
1 = Setpoint
P07
Additional user information
0 (no display)
0 = No display
1 = Temp. in °C / °F
2 = Outside temperature (via bus)
3 = Time of day (12h, via bus)
4 = Time of day (24h, via bus)
P08
Comfort basic setpoint
21 °C
5 ... 40 °C
P09
Minimum setpoint limitation in Comfort
(Wmin
Comf
)
5 °C
5 ... 40 °C
P10
Maximum setpoint limitation in Comfort
(Wmax
Comf
)
35 °C
5 ... 40 °C
P11
Setpoint of heating in Economy
(Wheat
Eco
)
15 °C
OFF, 5 °C…Wcool
Eco
P12
Setpoint of cooling in Economy
(Wcool
Eco
)
30 °C
OFF, Wheat
Eco
…40°C
P13 *** Electric heater in cooling mode
ON
OFF = disabled
ON = enabled
P14 Button
lock
(Press operating mode button for 3 seconds to lock or unlock
the buttons)
0 (Disabled)
0 = Disabled
1 = Auto lock
2 = Manual lock
** Without time schedule via KNX, Auto is equal to Comfort.
*** Parameter P13 is only displayed for application "2-pipe with el heater".
All temperature settings in increments of 0.5 °C.
The control parameters displayed depend on the DIP switch settings made
Please record all changes you make!
The thermostat can be used in systems either for heating only or cooling
only, manually selection of heating or cooling, or automatic heating / cooling
changeover. Depending on the selected application, the relevant modes are
available and can be adjusted by commissioning parameter P01 if needed.
The factory setting for 2-pipe application is "Cooling only", and for 4 pipe
application "Heating and Cooling"
If the room temperature displayed by the thermostat does not agree with the
temperature effectively measured (after min 1 hour of operation), the tem-
perature sensor can be recalibrated. With parameter P05 the temperature can
be adjusted by + or – 0.5 °C up to a maximum of + / - 3 °C.