4 specifications – Sanyo SANUPS E11A202U User Manual
Page 43

− 40 −
15.4 Specifications
Item
Standard or Performance
Notes
MODEL E11A202U001
E11A202U001J
(*6)
Output capacity
2.0kVA/1.4kW
Cooling system
Forced air cooling
Type of Input pulg
NEMA 5-20P
NEMA L5-30P
(*6) When the plug is NEMA_5-20, the
input and output voltage of UPS are
120V. only (For UL rules.)
Phases
Single phase, 2-wire
120V 100,110,115,120V
Voltage
-20% to +15% Double Conversion mode
±5% Economy /Active Filter mode
±10% Fixed Economy mode
User settable
(Rated voltage same as output voltage)
Frequency
50Hz or 60Hz
±10%: Double Conversion mode
±1, 3, 5%: Economy /Active Filter mode
Power requirements
1.8kVA
Max. capacity during battery charging
AC in
pu
t
Input power factor
0.95 or more
During rated output (*2)
Type of receptacle
NEMA 5-20R×4 NEMA
L5-30R×1
Phases
Single phase, 2-wire
Voltage
120V
100, 110, 115, 120V (*6) User settable
Voltage regulation
Rated voltage
±2%
Rated frequency
50Hz or 60Hz
Same as input frequency
(auto selection)
Frequency regulation
Rated frequency
±0.5% Double Conversion mode
Rated frequency
±1, 3, 5% Economy/Active Filter
mode
1, 3, 5% selectable
Internal oscillator accuracy
±0.5%
Voltage waveform
Sine wave
Distortion factor of voltage
waveform
Linear load: 3% or less
100% rectifier load: 7% or less
During rated output
Rapid load
change
0%
⇔ 100% at transient or output
switch
Power outage,
recovery
Rated voltage
±5 %
During rated output
Transient
voltage
variation
Rapid input
voltage change
±10% variation
Response time
5 cycles or less
Load power factor (lag)
0.7 (lag)
Variation range 0.7 (lag) to 1.0
Overcurrent protection
Auto switch to bypass circuit at 105% or more With auto return function
Inverter 105%
200ms
AC Ou
tpu
t
Overload
capability
Bypass 20A
or
more
Type
Small sealed lead battery
Rated capacity
10 A・h
20 hour ratio
Number
4 (12V per battery)
4 in direct series
Batte
rie
s
Backup time
5 minutes
At 25°C (77°F) ambient temperature,
rated load
Generated heat
250W
During Double Conversion mode
Input leakage current
3mA or less
Operating environment
Ambient temperature: 0 to 40°C (32 to 104°F)
Relative humidity: 20 to 90%
(*3)
Acoustic noise
45 dB or less
1 m (approx. 40 inches) from UPS front
panel, 'A' characteristics (linear load)
Safety standard
UL1778-4th/C22.2 No.107.3-05-2nd:2005
EMI standard
FCC Part 15,Sub partB,Class-A
And EN55022 Class-A
Other quotation standards
EN62040-1-1:2003 (For LVD)
EN50091-2:1995 (For EMC)
EN55024:1998/A1:2001/A2:2003 (For EMC)
EN55022:1994/A1:1995/A2:1997 (For EMC)
(*1): The inverter is capable of operation synchronized with AC input and instantaneous switchover
provided that the AC input frequency is within
±3% (or 1%, 3%, 5%, selectable) of the rated
frequency, and the AC input voltage is within +15% to-20% of the rated voltage.
The UPS enters battery operation with the AC input frequency is outside the specified range.
(*2): When input voltage waveform distortion is under 1%.
(*3): The UPS contains batteries. Battery service life will be foreshortened if the UPS is used in an
environment where the ambient temperature exceeds 30°C (86°F).
(*4): If grounded, the ground phase of the input and output must match according to UPS specifications.
*****continues to the following page.*****