P027, P028, P029 – Siemens Stober CombiDrive CM400/3 User Manual
Page 21: P031, P032, P035, P041, P042, P043, P044
4. Clear Text Display Module & System Parameters
English
© STÖBER plc 1997
19
05.02.01
Parameter Function
Range
[Default]
Description / Notes
P027
••••
Skip frequency 2 (Hz)
0 - 120.00
[0.00]
See P014.
P028
••••
Skip frequency 3 (Hz)
0 - 120.00
[0.00]
See P014.
P029
••••
Skip frequency 4 (Hz)
0 - 120.00
[0.00]
See P014.
P031
••••
Jog frequency right (Hz)
0 - 120.00
[5.00]
Jogging is used to advance the motor by small amounts. It is
controlled via the JOG button or with a non-latching switch on one of
the digital inputs (P051 to P053).
If jog right is enabled (DINn = 7), this parameter controls the frequency at
which the inverter will run when the switch is closed. Unlike other setpoints, it
can be set lower than the minimum frequency.
P032
••••
Jog frequency left (Hz)
0 - 120.00
[5.00]
If jog left is enabled (DINn = 8), this parameter controls the frequency at which
the inverter will run when the switch is closed. Unlike other setpoints, it can be
set lower than the minimum frequency.
P035
Reverse motor direction
0 - 1
[0]
0 = Normal direction control.
1 = Direction control is reversed.
P041
••••
Fixed frequency 1 (Hz)
0 - 120.00
[5.00]
Valid if P006 = 2 and P053 = 6 or 18 or P051 = P052 = P053 = 17.
P042
••••
Fixed frequency 2 (Hz)
0 - 120.00
[10.00]
Valid if P006 = 2 and P052 = 6 or 18 or P051 = P052 = P053 = 17.
P043
••••
Fixed frequency 3 (Hz)
0 - 120.00
[15.00]
Valid if P006 = 2 and P051 = 6 or 18 or P051 = P052 = P053 = 17.
P044
••••
Fixed frequency 4 (Hz)
0 - 120.00
[20.00]
Valid if P006 = 2 and P051 = P052 = P053 = 17.
P045
Inversion fixed setpoints for
fixed frequencies 1 - 4
0 - 7
[0]
Sets the direction of rotation for the fixed frequency:
FF 1
FF 2
FF 3
FF 4
P045 = 0
⇒
⇒
⇒
⇒
P045 = 1
⇐
⇒
⇒
⇒
P045 = 2
⇒
⇐
⇒
⇒
P045 = 3
⇒
⇒
⇐
⇒
P045 = 4
⇒
⇒
⇒
⇐
P045 = 5
⇐
⇐
⇒
⇒
P045 = 6
⇐
⇐
⇐
⇒
P045 = 7
⇐
⇐
⇐
⇐
⇒ Fixed setpoints not inverted.
⇐
Fixed setpoints inverted.
P046
••••
Fixed frequency 5 (Hz)
0 - 120.00
[25.00]
Valid if P006 = 2 and P051 = P052 = P053 = 17.
P047
••••
Fixed frequency 6 (Hz)
0 - 120.00
[30.00]
Valid if P006 = 2 and P051 = P052 = P053 = 17.
P048
••••
Fixed frequency 7 (Hz)
0 - 120.00
[35.00]
Valid if P006 = 2 and P051 = P052 = P053 = 17.
P050
Inversion fixed setpoints for
fixed frequencies 5 - 7
0 - 7
[0]
Sets the direction of rotation for the fixed frequency:
FF 5
FF 6
FF 7
P050 = 0
⇒
⇒
⇒
P050 = 1
⇐
⇒
⇒
P050 = 2
⇒
⇐
⇒
P050 = 3
⇒
⇒
⇐
P050 = 4
⇒
⇒
⇒
P050 = 5
⇐
⇐
⇒
P050 = 6 or 7
⇐
⇐
⇐
⇒ Fixed setpoints not inverted.
⇐
Fixed setpoints inverted.