Gas supply – Southbend SSB-45 User Manual
Page 6
S
PECIFICATIONS
R
ADIANT
S
TEAKHOUSE
B
ROILER
P
AGE
6
OF
20 O
WNER
’
S
M
ANUAL
1190950
(02/09)
If a ventilation canopy is used, it is recommended that the canopy extend 6" (152 mm) past the broiler and that the
bottom edge be located 6'6" (1980 mm) from the floor. Filters should be installed at an angle of 45° or more from the
horizontal. This position prevents dripping grease, and facilitates collecting the run-off grease in a drip pan under the
filter.
A strong exhaust fan tends to create a vacuum in the room and may interfere with burner performance or may
extinguish pilot flames. Fresh air openings approximately equal to the fan area will relieve such a vacuum. The
exhaust fan should be installed at least 2" (51 mm) above the vent opening on the top rear of the broiler.
If the broiler is connected directly to an outside flue, a CSA design-certified down draft diverter must be installed.
In case of unsatisfactory performance by any gas appliance, check the appliance with the exhaust fan turned OFF. Do
this only long enough to check whether doing so corrects any problems with equipment performance. Then turn the
exhaust fan back on and let it run to remove any exhaust that may have accumulated during the test.
G
AS
S
UPPLY
The broiler is design-certified for operation on natural or propane gases. The broiler is shipped configured and
adjusted for the type of gas specified by the purchaser, which is indicated on the serial plate (see Figure 1 on page 3).
Connect the broiler ONLY to the type of gas for which it is configured and adjusted.
Gas Type
Total BTU/hour
Burner Orifice
Bar Pilot.
Min. Supply Pressure
Manifold Pressure
Natural Gas
42,000 Per
Burner
No. 36 (P/N 1006436)
No. 75 (P/N 1176664)
7" W.C.
6" W.C.
Propane
36,500 Per
Burner
No. 51 (P/N 1006451)
No. 79 (P/N 1176665)
11" W.C.
10" W.C.
Models with a rear gas connection have a 1" rear gas connection to an external regulator that is located at the rear
bottom corner on the right side. Models with a front gas supply are connected by unions assembled to the front
manifold.
Minimum supply pressure is 7" W.C. for natural gas, 11" W.C. for propane. An external pressure regulator and shutoff
valve are provided. If using a flexible-hose gas connection, the inside diameter of the hose must not be smaller than
the connector on the broiler, and must comply with ANSI Z21.69. Provide an adequate means of restraint to prevent
undue strain on the gas connection. Test pressure should not exceed 14" W.C.
If applicable, the vent line from the gas appliance pressure regulator must be installed to the outdoors in accordance
with local codes, or in the absence of local codes, with the National Fuel Gas Code, ANSI Z223.1, Natural Gas
Installation Code, CAN/CGA-B149.1, or the Propane Installation Code CAN/CGA-B149.2, as applicable.
An adequate gas supply is imperative. Undersized or low-pressure lines will restrict the volume of gas required for
satisfactory performance. Fluctuations of more than 25% on natural gas or 10% on propane gas will create problems
and affect burner-operating characteristics. A 1/8" pressure tap is located on the manifold to measure the manifold
pressure. The supply line to the broiler should be no smaller than the inside diameter of the pipe on the broiler to
which it is connected.