NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

Note: Trim Thimble/

Extension To Desired Length

And Pitch At The Roof Line

14" Min.

Pitched Roof

Pitched Roof

Bow Roof

14" Min.

Outer Pipe Of

Chimney

Outer Pipe Of

Chimney

Outer Pipe Of

Chimney

14" Min.

Firestop

Thimble

Extension

13"

Firestop

Thimble

Firestop

Thimble

Thimble

SV-FSTFE

G. Continue installation of horizontal/inclined

sections - Continue with the installation of the

straight vent sections in horizontal/inclined run

as described in Step C. Install support straps

every 5 ft. (1.52 m) along horizontal/inclined

vent runs using conventional plumber’s tape.

See Page 19, Figure 34. It is very important

that the horizontal/inclined run be maintained

in a straight (no dips) and recommended to be

in a slightly elevated plane, in a direction away

from the fireplace of 1/4 " rise per foot (20 mm

per meter) which is ideal, though rise per foot

run ratios that are smaller are acceptable all the

way down to at or near level. Use a carpenter’s

level to measure from a constant surface and

adjust the support straps as necessary.

It is important to maintain the required clear-

ances to combustibles: 1" (25 mm) at all sides

for all vertical runs; and 3" (76 mm) at the top,

1" (25 mm) at sides, and 1" (25 mm) at the

bottom for all horizontal/inclined runs.

H. Frame roof opening - Identify location for

vent at the roof. Cut and/or frame opening per

Roof Framing Chart (Figure 26 on Page 16).

Twist elbow sections in a clockwise direction

only so as to avoid the possibility of unlocking

any of the previously connected vent sections.

See Figure 25.

Figure 25

7-5/8”

(194 mm)

4-13/16

(122 mm)

Swivel Joint

(360° swivel)

SV4.5E45

45° Elbow)

Swivel Joint

(360° swivel)

SV4.5E90

90° Elbow)

(206 mm)

8-1/8"

F. Change vent direction to horizontal/inclined

run - At transition from or to a horizontal/inclined

run, install the SV4.5E45 and SV4.5E90 elbows

in the same manner as the straight vent sections.

The elbows feature a twist section to allow them

to be routed about the center axis of their initial

collar section to align with the required direction

of the next vent run element.

Blocking

Support Straps

(Plumber's tape)

8 feet (2.4 m)

Maximum

1 inch (25.4

mm) minimum

clearance to

combustibles

Figure 24

Figure 22

14" Min.

Outer Pipe Of

Chimney

Use correct firestop

thimble depending on the

pitch of the interior

ceiling.

Note: Regular Thimble

(SV-FSTFE) Can Be Used

If A Header Is Constructed

At This Point

Figure 23

E. Support the vertical vent run sections

-Support the vertical portion of the venting

system every 8 feet (2.4m) above the fireplace

vent outlet using field provided support straps

(conventional plumber's tape). Secure the

plumber's tape to the framing members with

nails or screws. Loop the tape around the vent,

securing the ends of the tape to the framing.

If desired, sheet metal screws #6 x 1/2" length

may be used to secure the support straps to

the vent pipe. See Figure 24.