Wiring – Siemens OpenAir GND Series User Manual
Page 5
OpenAir GND Series Electronic Damper Actuator UL Listed Fire/Smoke Control Dampers
Technical Instructions
Document No. 155-746
March 17, 2005
Wiring
All wiring must conform to NEC and local codes and regulations.
Function Color
Supply Red
Neutral Black
Ground Green
Wire Designations
24 Vac/dc
M
BLACK
(NEUTRAL)
RED
(SUPPLY)
GREEN
(GROUND)
EA0941R1
Figure 2.
Function Color
Line Black
Neutral White
Ground Green
120 Vac
M
WHITE
(Neutral)
BLACK (Line)
GREEN
(Ground)
EA1167R2
Figure 3.
Function
Color
Line Brown
Neutral Blue
Ground Green
230 Vac
M
BLUE
(Neutral)
BROWN (Line)
GREEN
(Ground)
EA0609R2
Figure 4.
CAUTION:
The actuator must be wired
with a 230 Vac line with respect
to neutral and the ground lead
must be connected for proper
protection of the actuator. Any
other connection, such as
phase-to-phase, can damage
the actuator.
Auxiliary Switches
YELLOW
GRAY
85∞
5∞
EA1163R2
Figure 5.
Switch
Wire
Color
Switch
Makes
Switch
Breaks
5°
Gray
< 5°
> 5°
85°
Yellow > 85°
< 85°
NOTE:
Both sets of contacts are open when actuator is
between 5° and 85°.