OpenAir GND Series Electronic Damper Actuator UL Listed Fire/Smoke Control Dampers
Technical Instructions
Document No. 155-746
March 17, 2005
Specifications
Power supply
Operating voltage
24 Vac ±20%
24
Vdc
+20%,
-10%
120
Vac
±10%
230
Vac
±10%
Frequency 50/60
Hz
Power consumption
24 Vac/dc
running
20
VA/12W
holding
8
VA/6W
Power Consumption
120 Vac/230 Vac
running
20
VA
holding
9 VA
Function
Running torque
53 lb-in (6 Nm) (minimum)
Stall torque (minimum)
160 lb-in (18 Nm)
Torque reduction at elevated temperature
Less than 10%
Runtime for 90°
15 seconds nominal
closing (on power loss) with spring return
15 seconds maximum
Nominal angle of rotation
95°
Life Expectancy
Minimum 35,000 full stroke cycles
Mounting
Damper shaft size
.5-inch (12,7 mm) round
Damper shaft length, minimum
1.4-inch (36 mm)
Housing
Enclosure
NEMA 1
Material
Die cast aluminum alloy
Ambient conditions
Operation
0°F to 140°F (-18°C to 60°C)
one time 350°F (177°C)
Storage and transport
–40°F to 158°F (–40°C to 70°C)
Ambient humidity (non-condensing)
Maximum 95% rh non-condensing
Teflon® cable
400°F (200°C)
Agency certification
UL873
cUL C22.2 No. 24-93
AS/NZS
2064
1/2:1997
Conforms to CE requirements for the
EMC and low voltage directives
Australian Electromagnetic
Compatibility (EMC) per AS/NZS
4251.1/2:1999
(C-tick)
Miscellaneous
Pre-cabled connection
18 AWG, 3 feet (.9 meter)
3/8-in (.5mm) flexible conduit connector
Dimensions
9-in. × 3.25-in. × 3-in. D
(229 mm × 83 mm × 76 mm)
Weight
≈4 lb (1.8 kg)
Siemens Building Technologies, Inc.
Page 3 of 7