beautypg.com

2 introduction, 1 principle schematic, 2 description of main functions – Studer Innotec XPC 2200-48 User Manual

Page 6: Xp-compact, User manual xp-compact v5.1 e 5, Battery

background image

STUDER Innotec

XP-COMPACT

User manual

XP-COMPACT V5.1 E

5

2 Introduction

The XP-COMPACT is a sine wave inverter with integrated battery charger and solar charge con-
troller with many additional functions, it has been developed to be used as stand-alone (no grid
feeding) AC provider, or as continuous / break-free current supply provider (UPS).

2.1 Principle

schematic

Note:
(1) The neutral of the appliance is not connected to the earth whatever the functioning mode
is. If requested and according to the local regulation, an automatic connection between Neutral and
earth in inverter mode only may be done by installing a bridge internally to the unit. Please contact
your installer regarding this point.

2.2 Description of main functions

2.2.1 The

inverter

The sine wave inverter built in the XP-COMPACT generates a sinusoidal AC voltage with an ex-
ceptionally precise voltage and stabilized frequency. In order to start large electric motors, the user
has the possibility to employ a short-start-power which is 3-times the nominal power of the XP-
COMPACT.
The inverter is protected against overload and short-circuits. A power stage with the latest MOS-
FET power transistors, a toroidal transformer and a fast regulating system make-up a robust and
reliable inverter with highest efficiency. A 1-20 Watt adjustable charge detection system serves to
provide the smallest energy consumption and ensures a long life for the battery.

2.2.2 The transfer system

XP-COMPACT can be connected to an AC source, for example a stand-by emergency generator
or the AC network. With the transfer system, on one side you have an alternating voltage at the
output for use by the connected consumer appliances. On the other side the batteries are charged.
The distribution of energy between the consumer appliances and battery charger is automatic.

6p

8p

RJ11

OFF

AC OUT

Over Temp.

Overload

AC IN

SOLAR CHARGE

Contact manual

Contact active

Program

COMPACT

AUXILIARY CONTACT

ON/OFF

INVERTER - CHARGER

(Select)

RCC-01

INVERTER

CHARGER

(Program)

(Change status)

Battery
Low/High

RESET
ALARM

10

20

30

40

50

60

70

TRANSFER

C

h

a

rg

e

r

In

v

e

rt

e

r

5

10

20

40

60

80

100

130

160

A

%

EQUALIZE

L

PE

N

CT35

100nF

2,2nF

2n2nF

1uF

Fuse

1uF

2x2,7M

Temp.

Max. 6m

Max. 40m

L

PE

N

BATTERY

AUX. CONTACT

Remote control

SOLAR

AC OUT

AC IN

Transfer delay

Equalize

DC

AC

2,2nF

2n2nF

RJ45

2x2,7M

RCC-01

Internal bridge
Not mounted (1)

AC input line
grid or genset

AC output line

Auxiliary dry
contact

Solar generator

In

v

e

rt

e

r

/

c

h

a

rg

e

r

Microprocessor control
unit

Display

Filter

This manual is related to the following products: