Siemens SG020 User Manual
Page 21
Maintenance
Level 1
Level 2
Level 3
Level 4
Tasks
Recom-
Task
Required
Task
Required
Task
Task
mended
Comp.
to be done
Comp.
to be done
Comp.
Required
Comp.
to be done
(Date-
3 months/
(Date-
Semi-
(Date-
to be done
(Date-
monthly
Initials)
Break-in
Initials)
annually
Initials)
Annually
Initials)
10 Hrs.
30 Hrs.
50 Hrs.
100 Hrs.
1.
Disable the unit from
operating per the first page
warning.
2.
Check the engine oil level.
Adjust as necessary.
3.
Check the engine coolant
level. Adjust as necessary.
4.
Check the engine coolant
thermal protection level.
Correct as necessary.
5.
Check the natural gas
delivery system on gas
engine driven units.
Tighten connections as
necessary.
6.
Check the air inlets and
outlets for debris. Clean as
necessary.
7.
Check the battery
electrolyte level if
accessible. Adjust as
necessary.
8.
Check the battery posts,
cables, and charger for
loose connections,
corrosion, and proper
operation. Correct as
necessary.
9.
Check the unit wiring for
loose connections,
corrosion, and damage.
Correct as necessary.
10. Check the engine
accessory drive belts for
wear, weather cracking,
and damage. Replace as
necessary.
11. Visually inspect the unit
looking for leaks, wear or
damage, loose connections
or components, and
corrosion. Correct as
necessary.
12. Test the engine and
transfer switch safety
devices. Correct and/or
adjust as necessary.
11-2
Standby Generator Sets
Service Schedule
SrvSchd002 Re