Operation – SPX Cooling Technologies MARLEY AV 98-1514E User Manual
Page 17
17
produced by the entire tower would indicate. Wintertime operation of
multicell towers at low cold water temperature levels requires that the
operator be especially watchful.
2. As cold air enters the louvers, it causes the water flowing over the fill
to be drawn inward toward the center of the tower. Thus, under fan
operation, the louvers and lower periphery of the tower structure remain
partly dry, seeing only random splashing from within the tower—plus
normal atmospheric moisture from the entering air. Such lightly wetted
areas are most subject to freezing.
Therefore, if excessive ice forms on the louvers, stop the fan for a few
minutes. With the fan off, the water flow will increase in the vicinity of
the louvers and reduce the ice buildup.
3. Under extended extreme cold conditions, it may be necessary to op-
erate the fan in reverse. This forces warm air out through the louvers,
melting any accumulated ice—adequate heat load must be available.
Reversal may be at either full or half speed; however, SPX Cooling
recommends reversal at half speed. Reverse operation of the fan
should be used sparingly and should only be used to control ice,
not
to prevent it. Reverse fan operation should not need to exceed 1 or
2 minutes. Monitoring is required to determine the time required to
melt accumulated ice.
Reverse operation of fans for prolonged periods during subfreezing
weather can cause severe damage to fans and fan cylinders. Ice can
accumulate inside fan cylinders at fan blade plane of rotation and
fan blade tips will eventually strike this ring of ice, damaging the fan
blades or cylinder. Ice can also accumulate on fan blades and be
thrown off, damaging fan cylinder or blades. Allow a minimum of 10
minute delay between reverse operation and forward operation dur-
ing subfreezing weather to permit ice to dissipate from fan blades
and fan cylinders. See Caution note on page 11 for fan speed change
and reversing precautions.
Operation
Warning
➠