10
Product information CP 343–1
C79000–Z8964–C038–05
Note
Read the sections about downloading configuration data to the CP in the
NCM S7 for Industrial Ethernet manual /8/.
1.4
Further Information on Operation
Downloading Firmware
The CP 343-1 supports firmware updates using the Firmware Loader.
An update of the firmware can be downloaded from the PC/programming de-
vice at any time. After downloading the firmware, the CPU must be reconfigu-
red (power off/on or memory reset).
For more information on downloading the firmware, refer to the README file
of the NCM S7 for Industrial Ethernet configuration software.
Note
Read the information on downloading a database to the CP in the
NCM S7 manual /8/.
Group status “8183” on the FC call interface
The return values DONE=0; ERROR=1; Status=8183 can be caused by the
following states:
S
The CP is in the STOP mode.
S
The connection is not configured.
S
The connection is not established