Document No. 129-420
Installation Instructions
December 13, 2004

Manual Override

NOTE: When EAS is installed, you can still access the

manual override capability as shown in Figure
11.

0∞

0∞

GEB

GBB/GIB

GCA

GMA

EA1

185R1

Figure 11. Manual Override.

Auxiliary Switches

CAUTION:

There should be no load on the actuator
when setting the auxiliary switches.

Setting the Switches

With the actuator in the full-closed (0°) position, press in
and turn with a Phillips screwdriver to the desired
setting. Release pressure to set the switch.
The switch is now set.

~3.5

 mm

 

max.

 10N

EA1

186R1

5

25

45 55

65

75

85

35

15

85

75

65

55 45 35

25

15

5

5

25

45 55

65

75

85

35

15

85

75

65

55 45 35

25

15

5

Figure 12. Press In, Turn to Adjust, Release to Set Switch.

A

B

S1

S1

S4

S4

S2 S3

S2 S3

S5 S6

S5 S6

(Q12)

(Q14)

(Q14)

(Q12)

(Q22)

(Q24)

(Q22)

(Q24)

(Q1

1)

(Q1

1)

(Q21)

(Q21)

A

B

5∞

5∞

85∞

2∞

20∞

30∞

70∞

90∞

0∞

10∞

EA1

187R1

Figure 13. Example of Switches Set to 5° and 85°.

Wiring

WARNING:
Do not mix operations. Apply only line voltage
or only Class 2 voltages to the switching
outputs of both auxiliary switches A and B.

A

24 Vac...250 V/6(2) A

(Q12)

(Q14)

(Q24)

(Q22)

S2 S3

S5 S6

S1

S4

(Q1

1)

(Q21)

B

 

EA1

189R1

Figure 14. Wiring Diagram.

Wiring Designation

Wire Code

Color

Switch - Function

S1 Gray/red A

Input

S2

Gray/blue

A – NC

S3

Gray/pink

A – NO

S4 Black/red B

Input

S5

Black/blue

B – NC

S6

Black/pink

B – NO

Page 4 of 5

Siemens Building Technologies, Inc.