beautypg.com

Quickspecs – Server Technology QUICKSPECS BL20P User Manual

Page 31

background image

NOTE: Operating temperature has an altitude derating of 34° F per 1,000 ft (1° C per 304.8 m).
No direct sunlight. Upper operating limit is 10,000 ft or 70Kpa (3,048 m or 10.1 psia). Upper non-
operating limit is 30,000 ft or 30.3 KPa (9,144 m or 4.4 psia). Storage maximum humidity of 95%
is based on a maximum temperature of 113° F (45° C). Altitude maximum for storage is 70 KPa.

Operating and
Performance
Specifications for
Power Enclosures
(North America/Japan)

Single-Phase Model Three-Phase Model

Dimensions

Height

5.25 in (13.34 cm)

5.25 in (13.34 cm)

Width

17.60 in (44.7 cm)

17.60 in (44.7 cm)

Depth

27.15 in (68.96 cm)

27.15 in (68.96 cm)

Weights

No hot-plug power
supplies

47.5 lb (21.55 kg)

47.5 lb (21.55 kg)

All hot-plug power
supplies

99.5 lb (45.13 kg)

125.5 lb (56.93 kg)

Input requirements

Rated input voltage

200 VAC to 240 VAC 200 VAC to 240 VAC

line to line

Rated input frequency

50 Hz to 60 Hz

50 Hz to 60 Hz

Rated input current per
side

24A

24A per phase

Rated input power per
side

5760 W

9976 W

Power cord

1 IEC 309 3-pin, 32A
per side

1 IEC 309 5-pin, 32A
per side

Output voltage
specifications

Rated output voltage

-48.8 VDC to -54 VDC -48.8 VDC to -54 VDC

Rated output current

99A

170A

Rated output power

4298 W

8310 W

Nominal Power

4158 W at 208 VAC

7202 W at 208 VAC

Ambient Temperature
Range

(see NOTE)

Operating

50° to 95° F
(10° to 35° C)

50° to 95° F
(10° to 35° C)

Shipping

-22° to 140° F
(-30° to 60° C)

-22° to 140° F
(-30° to 60° C)

Relative Humidity non-
condensing

(see NOTE)

Operating

20% to 80%

20% to 80%

Non-operating

5% to 95%

5% to 95%

Wet Bulb Temperature Operating

82.4° F (28° C)

82.4° F (28° C)

Non-operating

101.7° F (38.7° C)

101.7° F (38.7° C)

NOTE: Operating temperature has an altitude derating of 34° F per 1,000 ft (1° C per 304.8 m).
No direct sunlight. Upper operating limit is 10,000 ft or 70Kpa (3,048 m or 10.1 psia). Upper non-
operating limit is 30,000 ft or 30.3 KPa (9,144 m or 4.4 psia). Storage maximum humidity of 95%
is based on a maximum temperature of 113° F (45° C). Altitude maximum for storage is 70 KPa.

QuickSpecs

HP ProLiant BL20p p-Class Server Blade

Technical Specifications

DA - 11411 Worldwide QuickSpecs — Version 24 — 9.24.2004