19 supply air blower performance (bq036, Belt drive) - side duct application, 20 supply air blower performance (bq036 – Johnson Controls SUNLINE 2000 BQ 060 User Manual
Page 25: Belt drive) - bottom duct application, 21 supply air blower performance (bq048, 22 supply air blower performance (bq048

364985-XIM-B-0508
Johnson Controls Unitary Products
25
TABLE 19: SUPPLY AIR BLOWER PERFORMANCE (BQ036 BELT DRIVE) - SIDE DUCT APPLICATION
Air
Flow
(CFM)
Available External Static Pressure - IWG
1
1. Blower performance includes 1” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
4. Field Supplied Drive.
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Supplied Drive
Standard Drive Option
HIgh Static Drive Option
800
678
0.37
761
0.44
840
0.52
917
0.60
991
0.69
1062
0.77
1130
0.87
1195
0.96
1259
1.06
1320
1.17
1000
699
0.42
782
0.49
862
0.56
939
0.64
1012
0.73
1083
0.82
1151
0.91
1217
1.01
1280
1.11
1341
1.21
1200
727
0.45
810
0.52
889
0.60
966
0.68
1040
0.76
1110
0.85
1179
0.95
1244
1.04
1308
1.14
1369
1.24
1400
759
0.51
842
0.58
922
0.65
998
0.73
1072
0.82
1143
0.91
1211
1.00
1276
1.10
1340
1.20
1401
1.30
1600
795
0.60
878
0.67
958
0.74
1035
0.82
1108
0.91
1179
1.00
1247
1.09
1313
1.19
1376
1.28
1438
1.39
FS
4
TABLE 20: SUPPLY AIR BLOWER PERFORMANCE (BQ036 BELT DRIVE) - BOTTOM DUCT APPLICATION
Air
Flow
(CFM)
Available External Static Pressure - IWG
1
1. Blower performance includes 1” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Supplied Drive
Standard Drive Option
HIgh Static Drive Option
800
661
0.39
751
0.45
838
0.53
922
0.61
1002
0.69
1079
0.78
1153
0.87
1225
0.96
1294
1.06
1361
1.16
1000
685
0.43
775
0.50
862
0.57
945
0.65
1025
0.73
1103
0.82
1177
0.91
1248
1.00
1317
1.10
1384
1.20
1200
714
0.46
805
0.53
892
0.60
975
0.68
1055
0.76
1132
0.85
1207
0.94
1278
1.04
1347
1.13
1414
1.23
1400
749
0.52
840
0.58
927
0.66
1010
0.74
1090
0.82
1167
0.91
1242
1.00
1313
1.09
1382
1.19
1449
1.29
1600
789
0.60
880
0.67
967
0.74
1050
0.82
1130
0.91
1207
0.99
1282
1.08
1353
1.18
1422
1.27
1489
1.37
Field Supplied Drive
TABLE 21: SUPPLY AIR BLOWER PERFORMANCE (BQ048 BELT DRIVE) - SIDE DUCT APPLICATION
Air
Flow
(CFM)
Available External Static Pressure - IWG
1
1. Blower performance includes 1” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Supplied Drive
Standard Drive Option
HIgh Static Drive Option
1000
656
0.41
757
0.46
851
0.52
937
0.58
1017
0.66
1092
0.73
1162
0.81
1228
0.90
1291
0.99
1351
1.08
1200
680
0.47
781
0.52
874
0.58
960
0.65
1041
0.72
1115
0.80
1185
0.88
1251
0.96
1314
1.05
1375
1.14
1400
706
0.56
807
0.61
901
0.67
987
0.73
1067
0.80
1142
0.88
1212
0.96
1278
1.05
1341
1.13
1401
1.22
1600
737
0.67
839
0.72
932
0.77
1018
0.84
1098
0.91
1173
0.99
1243
1.07
1309
1.15
1372
1.24
1433
1.33
1800
774
0.80
875
0.85
968
0.90
1055
0.97
1135
1.04
1209
1.12
1279
1.20
1345
1.28
1408
1.37
1469
1.46
2000
815
0.95
916
1.00
1010
1.06
1096
1.12
1176
1.19
1251
1.27
1321
1.35
1387
1.44
1450
1.52
1510
1.61
TABLE 22: SUPPLY AIR BLOWER PERFORMANCE (BQ048 BELT DRIVE) - BOTTOM DUCT APPLICATION
Air
Flow
(CFM)
Available External Static Pressure - IWG
1
1. Blower performance includes 1” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
4. Field Supplied Drive.
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Supplied Drive
Standard Drive Option
HIgh Static Drive Option
1000
638
0.42
748
0.47
849
0.53
944
0.59
1031
0.66
1112
0.74
1188
0.82
1260
0.90
1329
0.98
1395
1.07
1200
663
0.48
773
0.53
875
0.59
969
0.65
1056
0.72
1138
0.80
1214
0.88
1286
0.96
1354
1.04
1420
1.13
1400
692
0.57
802
0.61
904
0.67
998
0.73
1085
0.80
1167
0.88
1243
0.96
1315
1.04
1383
1.13
1449
1.21
1600
726
0.67
836
0.72
938
0.78
1032
0.84
1119
0.91
1201
0.98
1277
1.06
1349
1.15
1417
1.23
1483
1.32
1800
766
0.80
876
0.85
977
0.90
1072
0.97
1159
1.04
1240
1.11
1316
1.19
1388
1.27
1457
1.36
1523
1.45
2000
811
0.95
921
0.99
1023
1.05
1117
1.11
1204
1.18
1285
1.26
1362
1.34
1434
1.42
1502
1.51
1568
1.59
FS
4