364985-XIM-B-0508
22
Johnson Controls Unitary Products
TABLE 15: ELECTRIC HEAT CORRECTION
FACTORS
NOMINAL VOLTAGE
VOLTAGE
kW CAP. MULTIPLIER
208
208
0.75
240
230
0.92
480
460
0.92
600
575
0.92
TABLE 16: VOLTAGE LIMITATIONS
1
1. Utilization Range “A” in accordance with ARI Standard
110.
POWER SUPPLY
VOLTAGE
MIN.
MAX.
208/230-3-60
187
253
460-3-60
414
506
575-3-60
518
630
FIGURE 7:
UNIT DIMENSIONS (3 - 5 TON HEAT PUMP) FRONT VIEW