Remote condenser installation, Installation guidelines, Ice series general information – Ice-O-Matic ICE0250 Series User Manual
Page 20

ICE Series
General Information
Page A18
Remote Condenser Installation
For proper operation of the Ice-O-matic ice machine, the following installation guidelines must be
followed. Failure to do so may result in loss of production capacity, premature part failure, and
may void all warranties.
Installation Guidelines
Ambient operating temperatures: -20°F (-28.9°C) to 120°F (48.9°C)
Maximum refrigerant line length: 60 ft. (18.29 Meters)
Maximum vertical rise:
16 ft. (4.88 Meters)
Minimum condenser height:
ICE Series ice machine remote condensers must not be
installed more than 6 feet (1.3 meters) below the refrigerant line quick connects at the rear of the
ice machine. No part of the refrigerant lines, between the ice machine and the remote
condenser, should fall below this point. Condensers must have a vertical airflow.
Air Flow
- ICE 1806 (17 pages)
- EF 800 (2 pages)
- CD40522 (2 pages)
- ICE0520 (26 pages)
- ICE0405 (1 page)
- ICEU206 (17 pages)
- ICE 1406 (19 pages)
- ICEU305 (2 pages)
- Enodis (1 page)
- EMF 2306 (2 pages)
- GEM 0956 (45 pages)
- ICE1005 (2 pages)
- ICE1806/1807 (2 pages)
- MFI1255 (9 pages)
- GEM1256A/W/R (13 pages)
- ICE0320 (1 page)
- KBT22 (16 pages)
- ICE0520A3/W3 (11 pages)
- Counter Top Dispenser IOD16022 (13 pages)
- CD40230 (2 pages)
- ICE2106/2107 (2 pages)
- ICEU220 (2 pages)
- MFI1256 (2 pages)
- ICE0806 (2 pages)
- ICE0520W3 (11 pages)
- ICE0500A3-T3-W3-R4 (19 pages)
- EF Series (72 pages)
- ICEU070 (2 pages)
- EMF 800 (2 pages)
- ICE0500A4-T4-W4-R5 (19 pages)
- ICE0806A3-W3-R4 (19 pages)
- GEM1256R (50 pages)
- EMF 1106 Series (2 pages)
- ICEU225 (12 pages)
- ICEU220**2 (11 pages)
- MFI0500 (2 pages)
- VRC (17 pages)
- ICE2107 (17 pages)
- MFI (42 pages)
- IOD150 (2 pages)
- ICE0500 (2 pages)
- EMF 450 Series (2 pages)
- ICE0320/0325 (2 pages)
- CD40022 Series (12 pages)
- ICEU300**2 (11 pages)