#AASi
Command
#AASi
Description Reads the analog input or counter/frequency module data for all
channels from specified slot in the I-8000 unit.
#AASi[CHK](cr)
#
A delimiter character
AA
A 2-character HEX module address for the
specified I-8000 system ,ranging from 01 to FFh
Si
The specified slot number. i = 0 to 3 (4 slots) or
i = 0 to 7 (8 slots)
[CHK] 2-characters
of
checksum
Syntax
(cr)
Character Return(0x0D) for denote the end of
command
Valid Command
>(data)[chk](cr)
Invalid Command
?AA[CHK](cr)
Syntax error or communication error may get no response.
>
A delimiter for valid command
?
A delimiter for invalid command
AA
A 2-character HEX module address
(data)
A return string from the RTD input module in
engineering mode.
[CHK] A
2-character
checksum
(cr)
Carriage Return(0x0D) to denote the end of
response
Command
#01S3
Response
>+2.1234+2.1234 +2.1234 +2.1234 (cr)
Example
Description
The data read from analog data input module
i-87013 (4 channels analog input module) in slot 3
of the I-8000 system at address 01h is
+2.1234+2.1234 +2.1234 +2.1234.
Note: i-87013
Î 4-Channel RTD Analog Input Module
i-8017H
Î Fast 8-Channel mV/V/mA Analog Input Module
i-87017
Î 8-Channel mV/V/mA Analog Input Module
i-87018
Î 8-Channel mV/V/mA and Thermocouple Analog Input
Module
i-8080
Î 8-Channel Counter/Frequency Module
8430/8830/8KE4/8KE8 User’s manual, Jan 2005, Version 1.0, 8MS-002-10 ----- 72