#AASi
Command

#AASi

Description Reads the analog input or counter/frequency module data for all

channels from specified slot in the I-8000 unit.
#AASi[CHK](cr)
#

A delimiter character

AA

A 2-character HEX module address for the
specified I-8000 system ,ranging from 01 to FFh

Si

The specified slot number. i = 0 to 3 (4 slots) or
i = 0 to 7 (8 slots)

[CHK] 2-characters

of

checksum

Syntax

(cr)

Character Return(0x0D) for denote the end of
command

Valid Command

>(data)[chk](cr)

Invalid Command

?AA[CHK](cr)

Syntax error or communication error may get no response.
>

A delimiter for valid command

?

A delimiter for invalid command

AA

A 2-character HEX module address

(data)

A return string from the RTD input module in
engineering mode.

[CHK] A

2-character

checksum

(cr)

Carriage Return(0x0D) to denote the end of
response

Command

#01S3

Response

>+2.1234+2.1234 +2.1234 +2.1234 (cr)

Example

Description

The data read from analog data input module
i-87013 (4 channels analog input module) in slot 3
of the I-8000 system at address 01h is
+2.1234+2.1234 +2.1234 +2.1234.

Note: i-87013

Î 4-Channel RTD Analog Input Module

i-8017H

Î Fast 8-Channel mV/V/mA Analog Input Module

i-87017

Î 8-Channel mV/V/mA Analog Input Module

i-87018

Î 8-Channel mV/V/mA and Thermocouple Analog Input

Module
i-8080

Î 8-Channel Counter/Frequency Module

8430/8830/8KE4/8KE8 User’s manual, Jan 2005, Version 1.0, 8MS-002-10 ----- 72