11. The ammeter (Figure 46) will indicate zero amps with no

load applied. When a load is applied, this meter will
indicate the amount of current that the load is drawing
from the generator’s alternator.

Figure 49. Engine Tachometer

DCA-40SSAI — GENERATOR START-UP PROCEDURE

12. The engine oil pressure gauge (Figure 47) will indicate

the oil pressure (kg/ cm

2

)

of the engine. Under normal

operating conditions the oil pressure is approximately
25 psi.

13. The coolant temperature gauge (Figure 48) will indicate

the coolant temperature. Under normal operating
conditions the coolant temperature is between 165 and
215 degrees Fahrenheit.

WATER

TEMP

Figure 48. Coolant Temperature Gauge

Figure 47. Oil Pressure Gauge

14. The tachometer (Figure 49) will indicate the speed of

the engine when the generator is operating. Under normal
operating conditions this speed is approximately 1800
RPM’s.

16. Observe the generator's ammeter (Figure 51) and verify

it reads the anticipated amount of current with respect
to the load. The ammeter will only display a current
reading if the load is in use.

17. The generator will run until manually stopped or an

abnormal condition occurs.

Figure 50. Main and GFCI Circuit Breakers

Figure 51. Ammeter (Load)

A

0

40

60

75

20

15. Turn the MAIN, GFCI and LOAD circuit breakers to

their ON position (Figure 50).