PAGE 36 — DCA125USI 60 HZ GENERATOR • OPERATION AND PARTS MANUAL — REV. #1 (03/25/11)

GENERATOR SHUT-DOWN PROCEDURES

NORMAL SHUTDOWN PROCEDURE

To shutdown the generator, use the following procedure:

1. Place both the MAIN, GFCI and LOAD circuit breakers

as shown in Figure 54 to the OFF position..

Figure 54. Main, GFCI and Load

Circuit Breakers Off

2. Place the engine speed switch (Figure 55) in the “LOW

(down) position..

Figure 55. Ignition Switch (Normal)

3. Let the engine cool by running it at low speed for 3-5

minutes with no load applied.

4. Place

the

MPEC Control Switch (Figure 56) to the

OFF/RESET position.

Figure 56. MPEC Control Switch (Off/Reset)

5. Verify

that

all status LEDs on the MPEC display are

OFF (not lit).

6. Remove all loads from the generator.

7. Inspect entire generator for any damage or loosening of

components that may have occurred during operation.

EMERGENCY SHUTDOWN PROCEDURE

1. Place

the

MPEC Control Switch (Figure 56) in the

OFF/RESET position.

WARNING

NEVER stop the engine suddenly except in an
emergency.

12. The coolant temperature gauge (Figure 50) will

indicate the coolant temperature. Under normal
operating conditions the coolant temperature should
be between 167°~203°F (75°~95°C) (Green Zone).

Figure 50. Coolant Temperature Gauge

13. The tachometer gauge (Figure 51) will indicate the

speed of the engine when the generator is operating.
Under normal operating conditions this speed is
approximately 1800 RPM’s.

Figure 51. Engine Tachometer Gauge

14. Place the main, GFCI, and aux. circuit breakers in the

ON position (Figure 52).

Figure 52. Main, Aux. and GFCI

Circuit Breakers (ON)

15. Observe the generator’s ammeter (Figure 53) and

verify it reads the anticipated amount of current with
respect to the load. The ammeter will only display a
current reading if a load is in use.

Figure 53. Ammeter (Load)

16. The generator will run until manually stopped or an

abnormal condition occurs.