beautypg.com

MITSUBISHI ELECTRIC 9800A SERIES UPS User Manual

Page 32

background image


MITSUBISHI ELECTRIC 9800A SERIES UPS

MITSUBISHI
ELECTRIC

9800A SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

2-11

NOTE:

The UPS is equipped with a selectable output contact feature. The

above alarms are the default settings. Contact MITSUBISHI
ELECTRIC AUTOMATION, INC. for setup information

.

B) Input Contacts (for remote access of UPS)

External contacts are provided by the user of the UPS system. Terminal voltage at the
UPS is 24Vdc. Provide external dry contact accordingly.

NOTE:

Do not apply voltages to remote access input terminals. Damage to

UPS may result

.

Refer to Figure 2.17 for a typical wiring configuration. Although this figure applies to
the remote start/stop terminals, the same wiring arrangement is used for emergency
stop; battery liquid low; and battery temperature high.

FIGURE 2.17 Remote "Start" Contact Connections



Details of input contacts for remote access : TN2

Terminals 1 to 2

Remote "Inverter Start" input terminal (IN1)

Used to start inverter from a remote location. UPS must be programmed for
remote operation. Refer to Operations Menu for procedure.

Terminals 3 to 4

Remote "Inverter Stop" input terminal (IN2)

Used to stop inverter from a remote location. UPS must be programmed for
remote operation. Refer to Operations Menu for procedure.

Terminals 5 to 6

"Battery Temp. High" contact input (IN3)

Input fed by a thermocouple that monitors battery temperature. The
converter float voltage level is reduced for battery over-temperature
conditions. External thermocouple is user supplied

Start

Relay Coil current : 8.3mA

Use Momentary Switches Only

UPS Cabinet

External to UPS
Cabinet

Relay

Coil

24 VDC

Start

Switch

Common

User supplied

0.5S - 4S
ON
OFF