MITSUBISHI ELECTRIC 9800A SERIES UPS User Manual
Page 19
MITSUBISHI ELECTRIC 9800A SERIES UPS
MITSUBISHI
ELECTRIC
9800A SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
1-13
1.4 Specifications
The UPS name plate displays the rated kVA as well as nominal voltages and currents. The
name plate is located on the inside of the UPS front door.
TABLE 1.1 Power Specifications
Rated output
Power
Input voltage
3 phase / 3 wire
Bypass input voltage
3 phase / 4 wire
Output voltage
3 phase / 3 or 4 wire
100kVA / 80kW
150kVA / 120kW
225kVA / 180kW
300kVA / 270kW
375kVA / 338kW
500kVA / 450kW
750kVA / 675kW
480V
480V
480V
480V
480V
480V
480V
480V or 600V
480V or 600V
480V or 600V
480V or 600V
480V or 600V
480V or 600V
480V or 600V
480V or 600V
480V or 600V
480V or 600V
480V or 600V
480V or 600V
480V or 600V
480V or 600V
TABLE 1.2 UPS Module Information
UPS
[kVA]
CABLE
ENTRY
WIDTH
[in / mm]
DEPTH
[in / mm]
HEIGHT
[in / mm]
WEIGHT
[lb./ kg]
HEATING
[kBTU/h]
100
BOTTOM
43.3 / 1100
29.8 / 758
79.7 / 2025
2100 / 950
22.0
150
BOTTOM
47.2 / 1200
29.8 / 758
79.7 / 2025
2820 / 1275
33.0
225
BOTTOM
55.1 / 1400
29.8 / 758
79.7 / 2025
3310 / 1500
45.0
300
TOP
76.8 / 1950
37.7 / 958
79.7 / 2025
4990 / 2260
68.0
375
TOP
76.8 / 1950
37.7 / 958
79.7 / 2025
5250 / 2380
84.0
500
TOP
114.2 / 2900
37.7 / 958
79.7 / 2025
6930 / 3140
98.0
750
TOP
129.9 / 3300
49.5 / 1258
79.7 / 2025
9655 / 4380
136.1