Installation site, Confined space installation – Miele TOUCHTRONIC T 9822 User Manual
Page 10
Confined space installation
^ When installed in any space with less
than 122 square feet (11.3 m
2
),
minimum clearances around the
dryer must be adhered to for proper
ventilation and vents for make up air
must be installed.
^ Do not install any other fuel-burning
appliance in the same space as the
dryer.
Confined door openings
Any doors limiting circulation must be
louvered or otherwise ventilated.
A minimum of 200 square inches
(1,290 cm
2
) of opening is required. It
must be equally divided within 12"
(30.5 cm) from the top and bottom of
the door.
Minimum installation clearance
Sides: 0 " (0 cm)
Top:
12" (30.5 cm)
Rear: 0" (0 cm) (as close to wall as
gas connection and venting allows)
Front to door: 2" (5 cm)
Make sure the dryer door can open
completely once installed.
Exhaust duct clearance
to combustible material: 2" (5 cm)
Installation site
10