Page 17: Minimum hearth extension dimensions

background image

17

STR/CVR Series Woodburning Fireplaces

7412961

WARNING: HEARTH EXTENSION MUST BE IN-
STALLED IN ACCORDANCE WITH FIGURES 24 AND
25.
Alternate noncombustible materials may be used
providing the (total) thermal resistance (Rt value) of the
alternate material employed is greater than or equal to
R = 1.09. Thermal resistance (R) or thermal conductivity
(K), may be obtained from manufacturer of the material.
Factors are related by the formula K = 1/R.
T = given thickness
R = thermal resistance for a given thickness (T)
K = thermal conductivity
Noncombustible material with a lower R value may
be used, provided thickness of material is sufficiently
greater to maintain an equivalent (total) thermal resis-
tance (Rt).

Hearth Installation

A hearth extension is required to protect a combustible
floor in front of the fireplace. Refer to Figure 24 for mini-
mum dimensions and mounting detail.
Note: Hearth Extension must not cover the air inlet
opening of a fireplace.
The hearth extension described in Figure 24 must be a
durable noncombustible material with a minimum (total)
Rt value of 1.09; refer to Figure 25 for examples. The
overall height (above a combustible floor), depth and
width must be as indicated, with the extension centered
to the fireplace opening.
The top of the insulation material must be covered with
a noncombustible decorative covering or a piece of
.018” minimum sheet metal, to protect hearth extension
material. (Fig. 24)
Secure the hearth extension to the floor to prevent
shifting, using trim molding or other similar means at
three (3) outer edges. Seal crack between the fireplace
hearth and hearth extension with a noncombustible
material. (Figs. 24 and 26)

Minimum Wall Clearances

WITH

Noncombustible

Surround Facing

WITHOUT

Noncombustible

Surround Facing

Minimum Hearth Extension Dimensions

(for On-Site Construction)

G

H

G

J

Seal cracks

between the

fireplace

and hearth

extension with

noncombustible

material

Safety strips

must overlap

���

" minimum

May install

noncombustible

decorative

covering

OR .018" min.

sheet metal

Fireplace

Hearth

Combustible

Floor

Minimum

Insulation

Value "R"

4" MIN.

FP714

STR/CVR

6/4/98

Firebox

Opening

A - Min. clearance

to combustible

perpendicular wall

B - Min. clearance

to combustible

perpendicular wall when

using noncombustible wall shield*

Side

Wall

Side

Wall

F**

C**

E

E

D

4" BRICK

(Example material)

Combustible material permitted within shaded area.

* Noncombustible wall shield requires 1" CFM Corporation

EH2416 insulation (minimum R Value = 1.85) between

decorative noncombustible rigid covering and combustible wall.

Minimum height and width is 40" x 40".
** Dimension/degree of angle will vary depending on thickness

of noncombustible surround facing.

G

H

G

J

CVR

STR

4"

Shaded area starts

1/2" away from

edge of unit

A

B

C

D

E

F

G

H

J

K

STR33/36 CVR36

16"

12"

48°

41°

18"

14"

8"

16"

48"

24"

(406 mm) (305 mm)

(457 mm) (356 mm) (203 mm) (406 mm) (1219 mm) (610 mm)

STR42 CVR42

20"

12"

42°

35°

18"

14'

12"

20"

61¹⁄₂"

24"

(508 mm) (305 mm)

(457 mm) (356 mm) (305 mm) (508 mm) (1562 mm) (610 mm)

FP714

Fig. 24 Combustible side wall protection and hearth extension dimensions.