STR/CVR Series Woodburning Fireplaces

7412961

Side Wall Protection

All joints (top, bottom and sides) where wall or deco-
rative facing material meets fireplace surround must
be completely sealed with a noncombustible material.
(Figs. 20 and 24)
The special wall shield design described in Figure 20 is
an alternate method of adding protection to side walls
and can be used in place of the SP40 with the same
wall clearances specified for the SP40. Rt must =1.85
minimum.

Examples of wall shield insulation:

1. Manville - CERAFORM 126, K=.27,
1/2 inches thick
2. CFM Corporation - EH2416, K = .458,
1 inch thick required.

FP723

Fig. 23 Minimum firebox dimensions from combustible materials.

FP723

STR/CVR Side Wall clearances

6/21/98

A

A

B

B

C

C

C

D

Perpendicular Side Wall

Parallel Side Wall

Perpendicular Side Wall

Parallel Side Wall

STR Series

CVR Series

Minimum Dimensions to Side Walls

(for on-site contruction)

Model

STR33

STR36

STR42

CVR36

CVR42

Parallel Side Wall

A

44"

44"

44"

44"

44"

to Movable Doors

(1118 mm)

(1118 mm)

(1118 mm)

(1118 mm)

(1118 mm)

Perpendicular

B

16"

16"

20"

16"

20"

Side Wall to Firebox Opening

(406 mm)

(406 mm)

(508 mm)

(406 mm)

(508 mm)

Air Space to Sides

C

1/2"

1/2"

1/2"

1/2"

1/2"

or Back of Unit

(13 mm)

(13 mm)

(13 mm)

(13 mm)

(13 mm)

End Panel Parallel

D

--

--

--

36"

36"

to End of Unit

(914 mm)

(914 mm)