Floor protection – Nesco 6033 User Manual

Page 5

background image

USSC

5

FLOOR PROTECTION

The American Harvest Multifuel Stove may be installed on a combustible floor, with proper floor protection, or on a

masonry hearth. The hearth or non-combustible floor protector must extend a minimum of (6) inches (152mm)in front

and (6) inches (152mm) from each side of the ash removal door.

INSTALLATION REQUIREMENTS

CLEARANCES TO COMBUSTIBLES

The stove must be installed with the following minimum clearances to side and back wall combustible materials. NOTE:

These are minimum clearances to combustible walls established by the testing lab. The amount of room needed on the left

side of the unit to access the electrical panel is (6) six inches (152mm).

PARALLEL - A - Left Sidewall to Top Edge of Unit

6 in./152mm

B - Sidewall to Flue

6 in./152mm

C - Backwall to Flue

3 in./75mm

D - Backwall to Unit

9 in./228mm

E - Right Sidewall to Top Edge of Unit

2 in./50mm

CORNER - F - Adjacent Wall to Flue

3 in./75mm

G - Adjacent Wall to Unit

4 in./100mm

BACK WALL

SIDE WALL

SIDE WALL

Alcove / Backwall / Sidewall

Parallel / Alcove Installation

BACK WALL

Corner Installation