(BP) Latch Relay Contact Models

Primarily designed to maintain a specific temperature range by turning ON or
OFF heaters or coolers having 125 VAC circuitry, the SPLBP and 45TEBP
SWICHGAGE

®

models are applicable to a variety of situations where tempera-

tures are variable and controlling factors. As the pointer touches a preset high or
low limit contact/snap-switch, the magnetic latching relay sets or resets to latch

a heater or cooler ON or OFF. The relay unlatches, (resets) when the opposite
contact operates. Pictured below is a typical application.
For applications with higher voltages, a Murphy TR assembly can be used
in conjunction with any 4-1/2 in. (114 mm) dial SWICHGAGE

®

.

SPLC and SPLFC SWICHGAGE

®

temperature indicator gages include 2 pilot

duty, pointer-type limit contacts (one for high and one for low) that can be used
for alarm and/or shutdown. The SPLC and SPLFC models will complete a cir-
cuit when the gage pointer and either limit contact meet. This provides an elec-
trical signal to alert the operator of critical temperature conditions or, when
required, to shut-down the equipment.
Both limit contacts (high and low) are field adjustable by simply turning the
fingertip type knob to the desired point on the scale dial.
The graphic below shows details of a typical SPLFC SWICHGAGE

®

model.

The 45TE series SWICHGAGE

®

incorporates 2 SPDT snap-switches instead

of the pointer-type contacts of the SPL. Unlike the SPL that completes an elec-
trical circuit as soon as the pointer touches the contact, the 45TE trip point indi-
cators will stop the pointer movement slightly before the switches operate. As
temperature continues to increase (reaching high set point) or to decrease
(reaching low set point), the electrical circuit is then made. It provides the abili-
ty to set the trip point exactly with the indicator needle—no guessing or equip-
ment calibration is needed as on blind switches. The 45TE trip points (high and
low) can be easily set using its stacked knob adjustment. See the schematic
below for details.

How the SPL Works

How the 45TE Works

Capillary Tube

Low Limit

High Limit

Latching Relay

Terminal Block for

customer wiring

SPLBP

REMOTE COOLER

OFF

Power

Supply

ENGINE

Coolant line

TEMPERATURE

MURPHY

SWICHGAGE®

TULSA, U.S.A.

270

250

230

170

350

330

320

310

390

°C

°F

ON

Sensing Bulb

(not shown)

Pointer

SPL Series

High Limit

Contact

Adjustment

Dial Cutaway

to Show

Mechanism

Pointer

Low Limit

Contact

Adjustment

TEMPERATURE

MURPHY

SWICHGAGE®
TULSA, U.S.A.

270

250

230

200

170

350

600

700

800

900

°C

°F

45TE Series

High Limit

Snap-switch

Stacked Knob

Adjustment

Low Limit
Snap-switch

Dial Cutaway to

Show Mechanism

Pointer

High Trip Point

Indicator

Low Trip Point

Indicator

TEMPERATURE

MURPHY

SWICHGAGE®
TULSA, U.S.A.

270

250

230

200

170

350

600

700

800

900

°C

°F

SPLFC model shown

45TEF model shown