beautypg.com

Overload, Operating anomalies, Utility power present – MGE UPS Systems 14+ User Manual

Page 18: Device fault battery fault, No utility power present, Utility power outside limits

background image

MGE UPS SYSTEMS

Pulsar ESV 8+/11+/14+/22+ EB 22/EB 22XLA : 86-153277-00

18

overload

utility power present

operating anomalies

device fault

battery fault

1c

flashing

1g

on

1 beep every second

Pulsar switches off automatically after
operating in overload for approximately 5
min.

no utility power present

1c

flashing

1g

on

1 beep every second

Pulsar switches off automatically after a
length of time which depends on the level
of overload.

NOTE:
Overload occurs if the electricity
consumption of the load connected is
greater than the rated power of Pulsar.
To acknowledge the fault, push button

3

,

temporarily disconnected Pulsar from the
wall socket

5

, disconnect non-priority

loads and re-start Pulsar.

switch off Pulsar (push button

3

), dis-

connect from the wall socket (flex

5

), and

check that Pulsar has not short-circuited (dis-
connect all applications),

check the input fuse

6b

and replace it

with a fuse of the same rating or reset ther-
mal breaker 6 ,

re-start Pulsar.

A battery test is carried out while Pulsar, is in
start-up phase, then automatically every 7 days
(overhaul times adjustable using ESV Driver).
If a battery fault is detected, the following
occurs:

recharge your battery for 8 hours.
If battery fault persists, see next page.

utility power outside limits

1a

to

1g

off

continuous beep

after the start-up sequence, if the audio
warning device sounds continuously, check
the voltage and frequency of your utility
power
(see the § entitled "characteristics")
and/or recharge your battery for 8 hours.

Start/Stop control on onput
receptacles 1 and 2
(PowerShare)

You can use the applications included on
the CD-ROM to remote control the
Start/Stop sequences on output receptacles

7a

(or

7b

). If

7a

(or

7b

) is disabled

through software, front panel led

1f

(or

1e

) flashes, with 1 beep every second.

Beep can be deactivated by
"function" button 2 .

NOTE:
If the previous symptoms persist, contact
our after sales department.

1b

flashing

1g

on

1 beep every second

1a

flashing

1g

on

1 beep every second

This manual is related to the following products: