Master Bilt Refrigeration Solutions TAF-48 ERC2 User Manual

Page 11

background image

11

Minimum
Compressor
On Time

Con

Minimum time that

the compressor
remain turned on

Range: from 0 to 15 min

2 min.

Alarm Delay

ALrd

Time delay before

the alarm goes off
after the
temperature fall
off the two alarm
set points

Range: from 0 to 59 min

30 – for LT
45
– for MT

Compressor
Run Time

CPrn

Time the

compressor runs
between defrosts

12 – for MT

Number of
Defrosts

nodF

Number of defrosts

per day

from 0 to 8 (0 means 1 defrost

every 48 hours)

N/A – for LT
0 – for MT

Defrost Start
Time

dEF1-8

Start time of each

defrost

N/A

Defrost
Duration

dEFd

Defrost duration

time (back-up for
defrost
termination
temperature)

Range: from 0 min to 4 hours

35 – for LT
0
– for MT

Fan Delay

FAnd

Delay time for the

fan after defrost
(back-up for fan
cut-in
temperature)

Range: from 0 to 15 min

2 – for LT
0 – for MT

Pump Down

Pudn

Pump down duration Range: from 0 to 59 min

0 min.

Drip Time

driP

Drip time duration

Range: from 0 to 59 min

2 – for LT
0
– for MT

Setpoint
Differential

diF

°

Cut-in temperature

differential
Note: cut-in is cut-
out plus differential

Range: from 1 to 25

°

10

°

F–for LT

7

o

F – for MT

Temperature
Initiated
Defrost

tdEF

Temperature that

will initiate a
defrost cycle

Range: from – 40 to 40

°

F or – 40 to

4

°

C

N/A

Defrost
Termination
Temperature

dEF

°

Temperature in the

evaporator that
will terminate the
defrost cycle

Range: from 0 to 75

°

F or –18 to

25

°

C

50

°

F

Fan Cut-In
Temperature

FAn

°

Temperature in the

evaporator that
will turn the fan
on after defrost

Range: from – 40 to 60

°

F or – 40 to

23

°

C

30

°

F–for LT

60

o

F–for MT

Low
Temperature
Alarm

ALLo

Low temperature

setpoint that will
make the alarm go
off and the error
message appear on
the display

Range: from – 40 to 83

°

F or – 40 to

23

°

C

-40

°

F–for LT

32

o

F–for MT