To change the other parameters (Second Level) follow these steps:

Step 1

and

Press and hold SET and DOWN for 10 seconds. The display
will show

dSPL

Step 2

Press SET to change the parameter

Step 3

or

Press UP or DOWN to change the options, time or temperature
for the current parameter

Step 4

Press SET to accept the new value

Step 5

Press DOWN to go to the next parameter, then go back to Step
2. After the last parameter is displayed (

ALHi

), the display will

go back to the normal operating condition

Note: to scroll down the parameters without changing them, press the DOWN button.

List of Parameters
Here is a list of the parameters that can be changed in the Second Level of programming, as well as
their options and ranges.
Note: Master-Bilt’s Set point Temperature (

Set)

is set at a recommended –10

°

F at the

factory.

Parameter Displa

y

Symbo

l

Description

Range / Options

Master-

Bilt’s

Factory

Setting

Display Status

dSPL

Information shown

on the display
during operation
conditions

tdAy

– time-of-day

rSP

°

– zone temperature

CyCL

– cycle between time and

zone temperature

Epr

°

– evaporator coil temperature


rSP

Clock Format

CLHr

Time Format(12 or

24 hours mode)

12Hr

– AM/PM format

24Hr

– 24 hour format

12Hr

Temperature
Format

°

dSP

Temperature

degrees

°

F

– degrees Fahrenheit

°

C

– degrees Celsius

°

F

Defrost Type

dFtP

Type of defrost used

in the application

ELEC

– electric defrost / off cycle

HgAS

– hot gas defrost

ELEC

Fan Status
During Defrost

EFAN

Enable or not the

fan during defrost

no

– fan is turned off during defrost

yES

– fan remains on during defrost

No

– for LT

yES

–for MT

Fan Status
During Normal
Mode

CFAN

Enable or not fan during
normal compressor

on/off mode

on

– fan on during normal mode

CyCP

– fan cycles with compressor

on

Defrost
Interval

dFin

Type of defrost

interval

TdAy

– time-of-day setpoint

CPrn

– compressor run time

tdEF

– temperature initiated defrost

ddEF

– demand initiated defrost

ddEF

–for LT

CPrn

–for MT


Minimum
Compressor
Off Time

CoFF

Minimum time that

the compressor
remain turned off

Range: from 0 to 15 min

2 min.